STANDARD RISK



-
 
-












NOTE:
The unit must be installed, commissioned and stored in a room of area at least X m² (see Max Refrigerant Charge
table). The appliance may not be installed in an unventilated room smaller than X m² (see Min Room Area table).
h
0
Values depend on the installation type (eg:0,6 x floor standing installations.)
Refer to IEC 60335-2-40:2013 regulation.
MAX Refrigerant Charge (kg)
R32
LFL (kg/m) Height h
0
(m) Floor Area (m)
0.306
4 7 10 15 20 30 50
0.6 0.68 0.90 1.08 1.32 1.53 1.87 2.41
1.0 1.14 1.51 1.80 2.20 2.54 3.12 4.02
1.8 2.05 2.71 3.24 3.97 4.58 5.61 7.24
2.2 2.50 3.31 3.96 4.85 5.60 6.86 8.85
MIN Room Area (m)
R32
LFL (kg/m) Height h
0
(m) Total refrigerant charge (kg)
0.306
1.224 1.836 2.448 3.672 4.896 6.12 7.956
0.6 29 51 116 206 321 543
1.0 10 19 42 74 116 196
1.8 3 6 13 23 36 60
2.2 2 4 9 15 24 40