Chapter 3: Configuration and commissioning
60 2X-A Series Installation Manual
When there is a fire alarm in any zone that is not in test, the control panel
responds to the alarm event as configured.
Testing control panel input activation
To test activation of an input:
1. Determine the input functionality (consult your fire system installation details).
2. Select Service mode from the Test menu, and then select Local or Global.
Service mode ensures that outputs are not accidentally activated during input
tests. Set Service mode to Global to avoid local and network output
activation. For more information, see āActivating service modeā on page 62.
3. Activate the input device according to the device instructions.
4. Check that the control panel reports the input activation as expected (this
depends on the input configuration, device type, etc.).
When the test is complete, reset the control panel and exit service mode.
Testing control panel and loop output activation
To test activation of an output:
1. Select Test from the Main menu.
2. Select Output test from the Test menu, and then select Panel outputs or Loop
outputs.
3. Select the output you want to test, and then select YES (to activate the
output) or NO (to deactivate the output).
4. Press the jog dial again to end the test.
5. Press F2 (Exit) to exit the menu.
Testing output group activation
To test output group activation:
1. Select Test from the Main menu, and then select Output group.
2. Select the ID of the output group you want to test, and then select YES (to
activate the output group) or NO (to deactivate the output group).
3. Press the jog dial again to end the test.
4. Press F2 (Exit) to exit the menu.