Gree GMV6 DC Inverter VRF Units Service Manual
9
The above parameters are tested based on the standard connection pipe length. In the actual
project, the parameters should be corrected referring to the capacity correction for the long
connection pipe of units.
Specifications may be changed due to product improvement. Please refer to nameplates of the
units.
3 The Range of Production Working Temperature
Cooling
Heating
Ambient temperature
-5°C ~55°C DB
-30°C ~24°C DB
Indoor temperature
14°C ~25°C WB
15°C ~27°C DB
Indoor humidity
≤80%
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling
Ambient temperature: 16°C ~45°C
Heating
Ambient temperature: -7°C ~16°C
NOTE!
If exceeding the temperature range for working, the product may be damaged, which is not within
the warranty range.