EasyManua.ls Logo

ascon M4 series - Parameterisation Process

ascon M4 series
53 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
275..0
é 5:0
t.i.
é 5:0
p.b.
é 0
A3s.p
274.8
A.Man
O.C.
t.c.
é 1:00
t.d.
é 20
é 1:00
t.run
25
4 - Operations
4.4 PARAMETERISATION
A
The parameter setting procedure
has a timeout. If no keys are
pressed for, at least, 30 seconds,
the controller switches back, auto-
matically, to the operator mode.
After having selected the parame-
ter or the code, press $ and %
to display or modify the value (see
page 22) The value is entered when
the next parameter is selected, by
pressing the è key.
Pressing the í key, the next group
of parameters is presented on the
display.
Values
modification
Modification/
selection
enter
Prameter
menu
selection
35.0
p.b.
Parameter
value
Parameter
mnemonic
M4
Operator mode
Timer run/stop
(if option
installed)
Auto/Man
selection
(see page 24)
AL3 alarm threshold [1]
(see page 29)
Proportional band
(PID algorithm only)
0.5…999.9% of span
Integral time
(PID algorithm only)
0ff / 0.1…100.0 min
Derivative time
(PID algorithm only)
0.5…999.9% of span
Cycle time
(Time proportioning only)
1…200 sec
Overshoot control
(PID algorithm only)
0.01…1.00
Note
[1] It is not presented if the con-
troller has been configured
with alarm n° 2 not active or
of sensor break type. Digit
N/M of the configuration
code is assigned to 0 or 1.
[2] These values are not auto-
matically stored on the PID
menu parameters P.b., t.i, t.d.
M4UK.ed6 20-05-2005 11:43 Pagina 25