8.1 Error code display on LED wire controller
Inlet water temperature sensor failure
The sensor in open or short circuit
Check or change the sensor
Outlet water temperature sensor
failure
The sensor in open or short circuit
Check or change the sensor
Heating condenser sensor failure
The sensor in open or short circuit
Check or change the sensor
Gas return sensor failure
The sensor in open or short circuit
Check or change the sensor
Ambient temperature sensor failure
The sensor in open or short circuit
Check or change the sensor
Condenser gas exit sensor failure
The sensor in open or short circuit
Check or change the sensor
Antifreeze protection in Winter
Ambient temperature or water inlet
temperature is too low
Low ambient temperature protection
Ambient temperature or water inlet
temperature is too low
Cooling condenser temperature
too high protection
Cooling condenser temperature is
too high
Stop the heat pump and wait the
cooling condenser temperature
drop down
T2 water temp. Too low
protection under cooling mode
3. Water flow switch seized
1.Refrigerant is too much
2. Air flow is not enough
1.Discharge redundant refrigerant
from HP gas system
2.Clean the air exchanger
1.Refrigerant is not enough
2.Water flow is not enough
3. Filter jammed or capillary jammed
1.Check if there is any gas leakage ,
re-fill the refrigerant
2.Clean the air exchanger
3.Replace the filter or capillary
Low water flow, wrong flow
direction, or flow switch failure.
Check if the water flow is enough and
flow in right direction, or else the
flow switch could be failed.