ECO 6 – User and installation manual
Release 5.1 33
Nr
PAR
DESCRIPTION
MIN
MAX
UNIT
DEFAULT
1
ADR
Controller address
1
4
num
1
2
EVO
Display options
0
255
num
0
3
IS1
Inputs setup 1
0
255
num
0
4
IS2
Inputs setup 2
0
255
num
0
5
OS1
Outputs setup 1
0
255
num
0
6
OS2
Outputs setup 2
0
255
num
0
7
FOP
Fans setup
0
255
num
0
8
DOP
Defrost setup
0
255
num
0
9
ALH
High alarm limit
-50,0
50,0
°C
6,0
10
ALL
Low alarm limit
-50,0
50,0
°C
-2,0
11
ALD
Alarm delay
0
240
min
10
12
ADS
Alarm delay at power on
1
240
min
120
13
ADF
Alarm delay after defrost
1
240
min
15
14
BUR
Buzzer time replay
1
255
min
20
15
BUF
Buzzer time-out
1
255
min
2
16
HYH
Upper differential cooling action
0,0
9,9
°C
0,0
17
HYL
Lower differential cooling action
0,0
9,9
°C
0,0
18
HYC
Differential heating action
0,0
9,9
sec
0,0
19
DAC
Compressor off delay
1
30
sec
4
20
ADL
Anticycling
0
255
sec
60
21
CDE
Second compressor delay
0
90
sec
55
22
ASS
Compressor delay at power-on
0
255
min
60
23
CON
Compressor ON in probe failure
0
255
min
6
24
COF
Compressor OFF in probe failure
0
255
min
2
25
CPH
Max compressor usage in 24 hours
0
99
%
90
26
FAS
Evaporator fan setpoint
-50,0
50,0
°C
8,0
27
HFF
Differential evaporator fan
1,0
20,0
°C
5,0
28
FAD
Fan delay in S2 probe failure or uninstalled
0
255
sec
30
29
FSD
Fan stop temperature during defrost phase
-50,0
10,0
°C
-2,0
30
LBT
Lower evaporator temperature
-55,0
0,0
°C
-12,0
31
DOO
Door alarm time
1
255
sec
40,0
32
FCE
Condenser fan setpoint
0,0
60,0
°C
25,0
33
HYF
Differential condenser fan
1,0
20,0
°C
5,0
34
MCT
Higher condenser temperature
0,0
70,0
°C
40,0
35
DCN
Clogged condenser threshold
0,0
30,0
°C
20,0
36
DCR
Condenser differential recovery temperature
0,2
20,0
°C
10,0