EasyManua.ls Logo

ATI Technologies GasSens - Page 19

ATI Technologies GasSens
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GasSens Gas Detection System Section 2 - A14 Receiver Module
O & M Manual
A14-RK, 8/06 2 - 2
A1 A2 A3 TROUBLE
TB2
TB1 TB2
1: +12 Module Power positive (12 VDC) 1: A1 NO Alarm 1 normally open contact
2: C Module Power Common 2: A1 C Alarm 1 common
3: Earth Ground (REQUIRED) 3: A1 NC Alarm 1 normally closed contact
4: H+ Audible Horn positive 4: A2 NO Alarm 2 normally open contact
5: H- Audible Horn negative 5: A2 C Alarm 2 common
6: RR Remote Reset 6: A2 NC Alarm 2 normally closed contact
7: RR Remote Reset 7: A3 NO Alarm 3 normally open contact
8: MA+ 4-20 mA output positive 8: A3 C Alarm 3 common
9: MA- 4-20 ma output negative 9: A3 NC Alarm 3 normally closed contact
10: Earth Ground 10: TROUBLE NC trouble normally closed contact
11: TR Transmitter Input 11: TROUBLE C Trouble common
12: TR Transmitter Input 12: TROUBLE NO Trouble normally open contact
NOTE: Relay contact designation is shown for relays in normal mode of operation for relays A1,
A2 and A3. If fail-safe relay operation is selected, NO and NC designations are reversed
for that relay. The TROUBLE relay is set to fail-safe operation at the factory, and the
designation shown above is for the trouble relay in fail-safe mode.
Figure 2-2: Receiver Module Terminals (ATI-029)
CAUTION: Receiver modules MUST be connected to a secure earth ground. Terminal 3 of
TB1 in Figure 2-2 above must be connected to the earth ground terminal of
ATI's power supply module as shown in the connection diagram in Figure 1-3.
If the user is providing another 12 VDC supply, be sure that the receiver is
properly grounded.