EasyManua.ls Logo

Atlas Copco SF 17+ - Page 102

Atlas Copco SF 17+
114 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation method F according table B.52.1.
Single-core cables, touching in free air
Clearance to wall not less than one cable diameter
Maximum allowed current in function of the ambient temperature for installation method F
Ambient temperature
Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 110 A < 96 A < 87 A < 78 A < 67 A
35 mm² < 137 A < 119 A < 108 A < 97 A < 84 A
50 mm² < 167 A < 145 A < 132 A < 119 A < 102 A
70 mm² < 216 A < 188 A < 171 A < 153 A < 132 A
95 mm² < 264 A < 230 A < 209 A < 187 A < 161 A
120 mm² < 308 A < 268 A < 243 A < 219 A < 188 A
Calculation method for IEC:
Single supply cables (3 phases + PE - configuration (1)):
Add 10 % to the total current (I
tot
from the tables)
Install the prescribed fuse on each cable
Parallel supply cable (2 x 3 phases + PE - configuration (2)):
Add 10 % to the total current (I
tot
from the tables) and divide by 2
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Install fuses of half the size of the recommended maximum fuse size on each cable.
When using 2 x 3 phases + PE as in (3):
Add 10 % to the total current (I
tot
from the tables) and divide by √3
Multiply the ampacity of the cables with 0.8 (see table A.52.17 (52-E1))
Fuse size: the recommended maximum fuse size divided by √3 on each cable.
Size of the PE cable: use following rule of thumb:
For supply cables up to 16 mm²: same size as supply wires
For supply cables between 16 mm² and 35 mm²: 16 mm²
For supply cables larger than 35 mm²: half the size of the supply wires
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended)!
Example: For SF 22 FF 400 V 50 Hz IEC, I
tot
= 52 A, ambient temperature is 40 °C,
recommended fuse: maximum 63 A.
In case of single supply cables (3 phases + PE - configuration (1)):
I = 52 A + 10 % = 52 x 1.1 = 57.2 A
The table for installation method B2 allows a maximum current of 54 A for a 16 mm²
cable. For a cable of 25 mm², the maximum allowed current is 70 A, which is sufficient.
Therefore, use a 3 x 25 mm² + 16 mm² cable.
If method C is used, 16 mm² is sufficient (maximum 66 A at 40 °C). Use a 3 x 16 + 16
mm² cable.
Install 63 A fuses.
In case of parallel supply cables (2 x 3 phases + PE - configuration (2)):
I = (52 A + 10 %)/2 = (52 x 1.1)/2 = 28.6 A
Instruction book
100 2920 7140 52

Related product manuals