Operation and maintenance manual - EN
EN
www.atmos.cz
EN-11
• The safety thermostat - located on the fuel supply pipe of the burner, will shut down the burner if
its temperature is higher than 95 °C (55 °C for boilers DxxPX, PXxx). Thus, it protects the burner
from return ignition of pellets in the conveyor and at the same time from operation with clogged
flue gas exhaust from the boiler (e.g. in case of a failure to remove dust from the boiler, flue gas
duct and chimney). The safety thermostat will also put the burner out of operation in case the hose
between the burner and conveyor gets perforated to prevent flue gas from escaping to the boiler
room.
INFO - After any shutdown of the burner when an error message (ALARM) appears on
the display it is necessary to immediately find the cause and remove it. After removing the
cause of the error you can start the burner by merely turning off and on the burner switch,
which is located on the boiler panel.
Basic dimensions of the opening for installation of the burner in a boiler
In the case of the D14P, D14P Compact, P14, P14
Compact, D15P, P15, D20P, P20, D21P, D21P
Compact, P21, P21 Compact, D25P, D25P Compact,
P25, P25 Compact boilers the boiler comprises a
frame with a sealing cord - 18x32 mm.
The DC15EP, DC18SP, DC25SP, DC30SPX,
DC32SP, C18SP, C25SP, AC25SP, AC35SP,
KC25SP, KC35SP, D10PX, PX10, D15PX, PX15,
D20PX, PX20, D25PX, PX25 have Sibral sealing
under the boiler.
Gasification boilers with an adaptation for a pellet
burner newly feature a 16x16 mm sealing cord.
The old version of these boilers had a soft Sibral
sealing, similarly to DCxxSP(X)/(EP) boilers.