TESTING – this is a separate menu in which you can individually test individual elements of the
burner in case of unclear issues or faults.
CAUTION – During testing the burner is out of operation and therefore
before the start of testing let the burner properly burn out.
ON (START) / OFF (STOP) - switch on / switch off the burner
ON (START) – This is the command to switch on the burner. Confirm the switch-on command
by pressing the Enter key.
OFF (STOP) – This is the command to switch off the burner. Confirm the switch-off command
by pressing the Enter key.
PA R AM ETERS menu
• Parameter Т1 – time for feeding the ignition amount of pellets… (100 s)
• Parameter Т2 –
maximum time for ignition of pellets (then a new attempt for ignition follows)… (10 min)
• Parameter Т4
–
running time of the worm conveyor after a standstill interval - power control… (12 s)
• Parameter Т5 – rundown time of the fan after the STOP command - for optimal burning out of
pellets in the combustion chamber… (15 min)
• Parameter Т6
–
standstill time of the worm conveyor after a running interval - power control… (8 s)
• Parameter Т7 – time to achieve complete burning of the ignition amount of fuel… (30 s)
• Parameter Т8 – time of fixed start of the ignition spiral in case of insufficiently burned out
pellets in the combustion chamber after expiration of parameter T5 - only valid
for the first ignition attempt... (6 min)
• Parameter Т10
–
time for gradual increase of the power of the burner to the nominal value… (10 min)
if T10 = 0, the function is off.