Operation and maintenance manual - EN
EN
www.atmos.cz
EN-79
12 ALARM SAFETY
Disconnected end switch on the
burner body
Disconnected safety thermostat
(95 °C (55 °C for boilers
DxxPX, PXxx)) on the supply
pipe of pellets to the burner
Due to burning of poor-quality
pellets that produce cake and
prevent trouble-free burning of
pellets in the burner mouth the
supply hose gets subsequently
clogged and the temperature at
the safety thermostat rises
Clogged flue gas exhaust from
the boiler caused by obstructed
flue gas ways in the boiler, flue
gas duct or chimney by dust
and soot; the clogging causes
return flow of flue gas and heat
to the pellet supply hose and
subsequent disconnection of the
safety thermostat.
blown fuse for the fan
(0.8A - 1.0A)
Properly tighten the burner to
the boiler and check the contact
of the end switch. Check the
function of the sheet-metal stop
of the end switch
Clean the combustion chamber
of the burner, if necessary, empty
the supply hose of pellets, turn
off and on the main switch on
the boiler
Clean the combustion chamber
of the burner every day until you
have good-quality pellets made
of wood without bark (white
pellets) that do not produce cake
and where it is sufficient to clean
the burner mouth once every 2 to
4 weeks
Clean the whole boiler, flue gas
duct and chimney from dust and
soot, turn off and on the main
switch on the boiler
Check and change tha fan with
the fuse
13 HIGH FLUE
TEMP.!
This is not an error, but a message
that notifies the operator that the
maximum set temperature of flue
gas has been exceeded
If this message appears when
installing sensors TV and TS
on the accumulation tank - it
is a warning that has not yet
been activated function control
burner (boiler) by two sensors
on the accumulation tank (S15
= 2)
They have been interchanged
on the terminal board
Clean the boiler and then turn
off and on the main switch on
the boiler to clear the error
message
S15 parameter set from the
factory setting (S15 = 1) to the
value S15 = 2 - turn off and on
the main switch on the boiler
to clear the error message
Change the connection of the
sensor on the terminal board
and turn off and on the main
switch on the boiler to clear
the error message