Intelligent Pump Controller
L932/B
Ver.1.1
Installation & Operation Manual
INTELLIGNET PUMP
CONTROL PANEL
IP54
Before carrying out any installation or maintenance
operation, controller must be disconnected from the
power supply;
Don't open the cover during running the controller;
Don't put wire,metal bar filaments etc into the
controller;
Don't splash water or other liquid over the controller;
INTELLIGNET PUMP
CONTROL PANEL
IP54
Before carrying out any installation or maintenance
operation, controller must be disconnected from the
power supply;
Don't open the cover during running the controller;
Don't put wire,metal bar filaments etc into the
controller;
Don't splash water or other liquid over the controller;
L932/B
STORE
SET
3 8 0
V
1 6 0
A
AUTO
A
0 8
Bar
A
PUMP
B
B
Controladores Inteligentes de bombas

Questions and Answers

  • J
    Jose WilliamsAug 16, 2025
    What to do if the ATX Hydrosmart L932/B Control Panel is flashing 'OVER LOAD'?
    • M
      Megan TerrellAug 16, 2025
      If the ATX Control Panel displays a flashing 'OVER LOAD' message, it indicates that the real running ampere is higher than the calibrated running ampere, placing the pump in overload protection. The L932/B will attempt to restart the pump every 30 minutes until the running ampere returns to normal. Another possible cause is a jammed pump impeller, a dragging pump motor, or a broken pump bearing, in which case you should check the pump impeller or bearing.
  • M
    Mary StoneAug 19, 2025
    What to do if the ATX Hydrosmart L932/B Control Panel is flashing 'OPEN PHASE'?
    • K
      Kristi PatelSep 12, 2025
      If the ATX Control Panel displays a flashing 'OPEN PHASE' message, it means the power supply has lost a phase or the controller inlet wire or pump cable is broken. Report it to the power supply company or repair the inlet wire or pump cable.
  • D
    David AguilarAug 22, 2025
    What to do if ATX Control Panel is flashing 'UNDER V'?
    • J
      jbrownAug 22, 2025
      If the ATX Control Panel is flashing 'UNDER V', it means the real running voltage is lower than the calibrated voltage, and the pump is in an undervoltage protection state. Report the low line voltage to the power supply company. The L932/B will attempt to restart the pump every 5 minutes until the line voltage is restored to normal.
  • J
    jserranoAug 25, 2025
    What to do if the ATX Hydrosmart L932/B Control Panel is flashing 'OVER V'?
    • L
      Luis CarterAug 26, 2025
      If the ATX Control Panel displays a flashing 'OVER V' message, it indicates that the real running voltage is higher than the calibrated voltage, and the pump is in an overvoltage protection state. Report the high line voltage to the power supply company. The L932/B will attempt to restart the pump every 5 minutes until the line voltage is restored to normal.
  • M
    Michelle MccartyAug 28, 2025
    What to do if ATX Hydrosmart L932/B is flashing 'THREE PHASE UNBALANCE'?
    • M
      Mercedes GloverAug 28, 2025
      If the ATX Control Panel displays a flashing 'THREE PHASE UNBALANCE' message, it means the real voltage (or ampere) between the three phases (R/S/T) is not the same, and the difference is more than ±15%. Report this to the power supply company. The L932/B will attempt to restart the pump every 5 minutes until the voltage (or ampere) between the three phases is restored to normal.
  • Z
    zalexanderAug 31, 2025
    What does it mean if my ATX Control Panel is flashing 'PUMP STALLED'?
    • J
      jrobinsonAug 31, 2025
      If the ATX Control Panel displays a flashing 'PUMP STALLED' message, it indicates that the pump motor's running ampere increase was greater than the normal running ampere (calibrated ampere) by more than 200%. You should immediately cut off the power supply and repair or replace the pump.
  • M
    Mr. Todd Ray IVSep 3, 2025
    What does flashing 'DRY RUN' on my ATX Hydrosmart L932/B mean?
    • A
      Amanda KennedySep 3, 2025
      If the ATX Control Panel displays a flashing 'DRY RUN' message, it means the liquid level in the well or sump is below the pump intake, causing the pump to stop running. The L932/B will attempt to restart the pump every 30 minutes until the liquid level rises above the pump intake.
  • H
    Holly StephensSep 6, 2025
    Why is the ATX Control Panel flashing 'REPEATED START'?
    • H
      Hector SingletonSep 6, 2025
      If the ATX Control Panel displays a flashing 'REPEATED START' message, it means the pump is starting more than 5 times per minute. The most common cause is a waterlogged tank. Check for a ruptured bladder in the water tank. Also, check the air volume control or snifter valve for proper operation, and examine the setting on the pressure switch for defects. Cut off the power supply and repair the water tank, pressure switch, or valve.
  • J
    jcolemanSep 9, 2025
    How to fix 'PHASE REVERSAL' flashing on ATX Control Panel?
    • D
      dpottsSep 9, 2025
      If the ATX Control Panel displays a flashing 'PHASE REVERSAL' message, it indicates an error in the sequence of the three-phase input voltage (R/S/T). To resolve this, change the sequence of the three phases (R/S/T).
  • L
    laurahughesSep 12, 2025
    What does 'ON LINE' mean on my ATX Hydrosmart L932/B?
    • A
      Andrea Johnson MDSep 12, 2025
      If the ATX Control Panel displays 'ON LINE', it means there is no communication link between the SC/computer and the L932/B. To resolve this, connect the L932/B to the SC/computer to enable long-distance monitoring.

Summary

Controller Components Overview

2 Installation Procedures

Power and Pump Electrical Connections

Guide on wiring the controller to the main power supply and connecting it to the electrical pumps.

Parameter Calibration

Setting and Erasing Pump Calibration

Step-by-step guide for setting and erasing pump calibration parameters for optimal protection.

3 Electrical Connections

Pressure Transmitter Installation

Booster Pumping System Wiring

Electrical Connection Diagram

Illustrates the electrical connections for a pressure booster pumping system, including probes and pumps.

4 Setting Working Pressure Values

Cut-Off Pressure Setting

Procedure for configuring the pressure value at which the pump system will shut off.

1 st Pump Cut-In Pressure Setting

Procedure for setting the pressure value for the first pump to start operation.

2 nd Pump Cut-In Pressure Setting

5 Basic Operation Modes

Auto Mode Logic Explained

Pump Protection Functions

Describes the controller's safety features against dry run, overload, and voltage issues.

6 Communication Link Features

Passive Dry Contact Connection

8 Troubleshooting Guide

Voltage and Phase Faults

Troubleshooting steps for under/over voltage, open phase, and phase reversal errors.