5-3
ACT1(Alarm Active 3
setting page )Default=HI
1.Decide active 3 with
or
key(HI or LO)
2.Press
key enter data and into ACT4 setting page
5-4
ACT2(Alarm Active 4
setting page )Default=HI
1.Decide active 4 with
or
key(HI or LO)
2.Press
key enter data and into HYS1 setting page
5-5
HYS1(Alarm Hysteresis 1
setting page)Default=0
1.Decide Hysteresis 1 with
or
or
key(0~999)
2.Press
key enter data and into HYS2 setting page
5-6
HYS2(Alarm Hysteresis 2
setting page)Default=0
1.Decide Hysteresis 2 with
or
or
key(0~999)
2.Press
key enter data and into HYS3 setting page
5-7
HYS3(Alarm Hysteresis 3
setting page)Default=0
1.Decide Hysteresis 3 with
or
or
key(0~999)
2.Press
key enter data and into HYS4 setting page
5-8
HYS4(Alarm Hysteresis 4
setting page)Default=0
1.Decide Hysteresis 4 with
or
or
key(0~999)
2.Press
key enter data and into DEL1 setting page
5-9
DEL1(Alarm Delay 1
setting page)Default=0
1.Decide delay 1 with
or
or
key(0~99.9 sec)
2.Press
key enter data and into DEL2 setting page
5-10
DEL2(Alarm Delay 2
setting page)Default=0
1.Decide delay 2 with
or
or
key(0~99.9sec)
2.Press
key enter data and into DEL3 setting page
5-11
DEL3(Alarm Delay 3
setting page)Default=0
1.Decide delay 3 with
or
or
key(0~99.9 sec)
2.Press
key enter data and into DEL4 setting page
5-12
DEL4(Alarm Delay 4
setting page)Default=0
1.Decide delay 4 with
or
or
key(0~99.9sec)
2.Press
key enter data and into SB setting page
5-13
SB(Start band)
Default=0
1.Decide start band with
or
or
key(-999~999)
2.Press
key enter data and into SDT setting page
5-14
SDT(Start Delay Time)
Default=0
1.Decide start delay time with
or
or
key(0~99.9sec)
2.Press
key enter data and return ROP setting group
6
AOP(Analog output setting
group)
Press
key decide AOP setting group , press
key into
ANLO setting page
6-1
ANLO(A/O Zero According
to Display setting
page)Default=0
1.Decide ANLO with
or
or
key(-19999~19999)
2.Press
key enter data and into ANHI setting page
6-2
ANHI(A/ O Span According
to Display setting
page)Default=0
1.Decide ANHI with
or
or
key(-19999~19999)
2.Press
key enter data and return AOP setting group
7
DOP(Communication
setting group)
press
key decide DOP setting group,press
key into
ADDR setting page
7-1
ADDR(Communication
Addr
ess setting page )
Default=0
1.Decide address with
or
or
key(0~255)
2.Press
key enter data and into BAUD setting page
7-2
BAUD(Communication Baud
Rate setting page)Value
on Default=19200
1.Decide baud rate with
or
key(19200,9600,4800,2400)
2.Press
key enter data and into PARI setting page
7-3
PARI(Communication
Parity Check setting
page)Default=n82
1.Decide parity check with
or
key(n82,n81,even,odd)
2.Press
key enter data and return DOP setting group
Step Parameter mark description Parameter mark
Operation manual
8 Normal display
Press
/ALARM key about 3 sec,into AL1 setting page
8-1
AL1 (Alarm value 1 setting
page) Default=0
1.Decide alarm value 1 with
or
or
key(-19999~19999)
2.Press
key enter data and into AL2 setting page
8-2
AL2 (Ala
rm value 2 setting
page) Default=0
1.Decide alarm value 2 with
or
or
key(-19999~19999)
2.Press
key enter data and into AL3 setting page
8-3
AL3 (Alarm value 3 setting
page) Default=0
1.Decide alarm value 3 with
or
or
key(-19999~19999)
2.Press
key enter data and into AL4 setting page
8-4
AL4 (Alarm value 4 setting
page) Default=0
1.Decide alarm value 4 with
or
or
key(-19999~19999)
2.Press
key enter data and return normal display