EasyManua.ls Logo

AXIOMET AX-3003P - Page 5

AXIOMET AX-3003P
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.2. Output Current Setting
Press key [V-Set/I-Set] until “Current” is shown on the LCD.
Setting method 1: Press [Number key (current value)] [En-
ter] to set output current.
Setting method 2: Press [Number knob (current value)] to
change the output current setting immediately. When use
this method with the output ON, the output current will be
changed following the input value by rotating the knob.
For example: Set output current to 3.200A.
Press [I-Set] [3] [.] [2] [0] [0] [Enter].
8.3. Over Voltage Protection Setting
Press key [OVP], to set the maximum output voltage. If the
adjusted value or actual output value is more than the max-
imum value, the output voltage will automatically stop, the
OVP indicator turns on, and warning signal by the beeper
will be heard.
Press key [OVP/OCP] until “OVP Set” is shown on the LCD.
Setting method 1: Press [Number key (voltage value)] [En-
ter] to complete OVP setting.
Setting method 2: Press [Number knob (voltage value)] to
change OVP setting immediately.
For example: Set over voltage protection value to 33.0V.
Press [OVP] [3] [3] [.] [0] [Enter].
8.4. Over Voltage Protection Status Setting
Press key [Menu] until “OVP Status” is shown on the LCD,
to proceed over voltage protection status setting, then press
[On/Off] to turn on or off the OVP function.
8.5. Over Current Protection Setting
Press key [OCP], to set the maximum output current. If the
adjusted value or actual output value is more than the max-
imum value, the output current will automatically stop, the
OCP indicator turns on, and warning signal by the beeper
will be heard.
Press key [OVP/OCP] until “OCP Set” is shown on the LCD.
Setting method 1: Press [Number key (current value)] [En-
ter] to complete OCP setting.
Setting method 2: Press [Number knob (current value)] to
change OCP setting immediately.
For example: Set over current protection value to 3.30A.
Press [OCP] [3] [.] [3] [0] [Enter].
8.6. Over Current Protection Status Setting
Press key [Menu] until “OCP Status” is shown on the LCD,
to proceed over current protection status setting, then press
[On/Off] to turn on or off the OCP function.
8.7. Voltage/Current Delay Time Setting
Press key [Delay], “Delay” is shown on the LCD.
Setting method 1: Press [Number key (delay time)] [Enter]
to complete voltage and current delay time setting.
Setting method 2: Press [Number knob (delay time)] to
change voltage and current delay time setting immediately.
For example: Set the delay time to 99999s.
Press [Delay] [9] [9] [9] [9] [9] [Enter].
Note: The Delay setting is effective only under the Auto
running operation, therefore, during the storage proceed-
ing, the Delay setting will be saved to the memory address
simultaneously.
8.8. Function Setup
Press [Shift] [Menu], proceed to the function setting, then
press [Menu] to select the options under the current function.
8.9. Voltage Step Setting
Set the maximum value of Step to be the rating value of the
setting range.
Press key [Menu] until “Utility V Step is shown on the
LCD.
Setting method 1: Press [Number key (voltage value)] [En-
ter] to set step voltage.
Setting method 2: Press [Number knob (voltage value)] to
change step voltage immediately.

Related product manuals