6-7
Chapter 6: Cautions regarding Explosion-Proof Models
Caution
•
Use the FM intrinsic safety explosion-proof model device with a barrier that satis-
fies the specifications below.
For models those date of manufacture are before September 2017
Input signal circuit:
Model AVP300/301 12.02 ≤ V
max
≤ 30 V, I
max
= 100 mA, Pi = 1 W, Ci = 0, Li = 0.22 mH
Model AVP302 12.02 ≤ V
max
≤ 30 V, I
max
= 100 mA, Pi = 1 W, Ci = 0.07 μF, Li = 0.22 mH
Travel transmission circuit:
Model AVP301 V
max
≤ 30 V, I
max
= 100 mA, Pi = 1 W, Ci = 0.07 μF, Li = 0.22 mH
For models those date of manufacture are after October 2017
Input signal circuit:
Model AVP300/301 12.02 ≤ V
max
≤ 30 V, I
max
= 100 mA, Pi = 1 W, Ci = 18.26 nF, Li = 0.22 mH
Model AVP302 12.02 ≤ V
max
≤ 30 V, I
max
= 100 mA, Pi = 1 W, Ci = 41 nF, Li = 0.22 mH
Travel transmission circuit:
Model AVP301 V
max
≤ 30 V, I
max
= 100 mA, Pi = 1 W, Ci = 22 nF, Li = 0.22 mH
• Perform electrical wiring in accordance with the NEC.