2-19
Chapter 2: Installation
Adjusting length of remote cable
Step Procedure
1 Remove the remote cable from the terminal box, and then cut a remote cable of a suitable
length.
2 Strip off about 6 cm of the sheath from the end of the cable, and strip off about 5 mm of
the insulation of the wire.
3 Insert the drain wire into the heat-shrinkable tubing, and shrink the heat-shrinkable
tubing by applying an appropriate amount of heat to it. (If there is no heat-shrinkable
tubing, take measures so that the drain wire can be insulated from the other wires.)
4 Crimp the wires and the RAV1.25-4 crimp terminals (wire diameter 1.25 mm, M4 round
crimp terminals) with an appropriate crimping tool.
Figure 2-19. Adjusting the Length of the Cable
Caution
When connecting or disconnecting positioner body cables, do not allow contami-
nants, rainwater, and the like to enter the valve travel detector unit or the positioner
body.
Periodically tighten the watertight gland and flameproof cable gland. Failure to do
so may allow rainwater to enter the equipment, resulting in malfunctions.
The cable cannot be removed from the valve travel detector unit. However, the wa-
tertight gland can be removed.
Do not remove the flameproof cable gland on the valve travel detector. Doing so
could cause wires inside the cable to be broken as a result of the rotation of the
cable.