3-4
Table 3-2. Remote Type settings
Valve travel
Direction
position
Lever
Position
Lever
Movement
Valve
direction
Valve Control Action
Setting
Actuator
Action
Valve
Action
Front Right
Up → Down Closed → Open
Direct
(Closed: 20 mA; open: 4 mA)
Reverse Reverse
Reverse
(Closed: 4 mA; open: 20 mA)
Direct Reverse
Up → Down Open → Closed
Direct
(Closed: 20 mA; open: 4 mA)
Direct Direct
Reverse
(Closed: 4 mA; open: 20 mA)
Reverse Direct
Rear Left
Up → Down Closed → Open
Direct
(Closed: 20 mA; open: 4 mA)
Reverse Reverse
Reverse
(Closed: 4 mA; open: 20 mA)
Direct Reverse
Up → Down Open → Closed
Direct
(Closed: 20 mA; open:4 mA)
Direct Direct
Reverse
(Closed:4 mA; open: 20 mA)
Reverse Direct
Front Left
Up → Down Closed → Open
Direct
(Closed: 20 mA; open: 4 mA)
Direct Direct
Reverse
(Closed: 4 mA; open: 20 mA)
Reverse Direct
Up → Down Open → Closed
Direct
(Closed: 20 mA; open: 4 mA)
Reverse Reverse
Reverse
(Closed: 4 mA; open: 20 mA)
Direct Reverse
Rear Right
Up → Down Closed → Open
Direct
(Closed: 20 mA; open: 4 mA)
Direct Direct
Reverse
(Closed: 4 mA; open: 20 mA)
Reverse Direct
Up → Down Open → Closed
Direct
(Closed: 20 mA; open: 4 mA)
Reverse Reverse
Reverse
(Closed: 4 mA; open: 20 mA)
Direct Reverse