E6
https://www.azbil.com
(10)
1st edition: Feb. 2018 (F)
5th edition: Apr. 2019 (V)
 z LAN interface communication specifications
Ports: 2 (LAN1, LAN2)
Communication path type:
IEEE802.3
10BASE-T/100BASE-TX (with Auto 
Negotiation and Auto MDI/MDI-X 
functions)
Connector: RJ-45
Cable: 100BASE-TX cable
UTP cable (4P), Cat 5e min. (straight) 
(both ends, ANSI/TIA/EIA-568B), 
100m max.
 z RS-485 interface communication specifications
Ports: 2 (RS-485 CH1, RS-485 CH2)
Network: Multidrop (up to 31 slave stations for 1 
master station)
Signal level: RS-485 compliant
Communications/synchronization type:
Full-duplex, start/stop synchronization 
(protocol: half-duplex)
Maximum cable length:500m
No. of wires: 3
Terminating resistor: External (150Ω 0.5W min.)
Transmission speed: Selectable from 4800, 9600, 19200, 
38400, 57600, and 115200 bps
Data bits: 7bits/8bits
Stop bits: 1bit/ 2bits
Parity bit: Even parity, odd parity, or non-parity
 z Battery*
Model: CR1632 (manufacturer: Panasonic or 
Maxell)
Please contact us if you can not obtain 
the battery.
Used for: Clock IC backup
• 
No battery is needed if you set the 
time using the time setting function 
at power-on.
• 
No battery is needed if inaccurate 
time of the history data can be 
tolerated.
* Not included with the product. Please purchase a commercially 
available battery that conforms to UL 1642 (CCN: BBCV 2).
 z Separately sold product
SLP-SVGJ91 Smart Loader Package
  External Dimensions
  Unit: mm
(20)
10)
5
R-REM-A2B-A137
 © 2018-2019 Azbil Corporation. All Rights Reserved.