Extended Shutdown
Perform the following services whenever the unit is shutdown in
excess of three days:
If the unit is mounted on vibration isolators or isolation rails (by
others), refer to the manufacturer’s guidelines before loading/
unloading weight from the unit.
Disconnect, lock-out, and tag-out all fans and pumps.
Close the shut-off valve in the make-up water line (supplied by
others), and drain the cold water basin and all exposed water
piping. Heat trace and insulate all exposed piping.
Clean all the debris, such as leaves and dirt, from the interior and
exterior of the unit.
Leave the cold water basin drain open so rain and melting snow will
drain from the unit.
Clean the basin strainer and re-install.
Cover the fan discharge to keep out dirt and debris.
For belt driven units, lubricate the fan shaft bearings, motor base,
and motor base adjusting screw.
Apply RUST VETO
®
to steel shafts.
Inspect the protectivenish on the unit. Clean and renish as required.
Maintain the fan motor starting device in the “OFF” position to
ensure personal safety in the case of future inspection or service.
Operation and Maintenance
Initial & Seasonal Start-Up
Start-up
Extended Shutdown
WARNING: Rapid on-off cycling
can cause the fan motor to
overheat. It is recommended that
controls be set to allow a max of 6
on-off cycles per hour.