EasyManua.ls Logo

BAC VX Series - Spray Nozzles and Heat Transfer Section

BAC VX Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
W W W . B A L T I M O R E A I R C O I L . C O M . A U
M A R 1 1 3 - 0
Figure 8. Nozzle Spray Distribution
Spray Nozzles And Heat Transfer Section
The spray nozzles and heat transfer section should be inspected and
cleaned each month. The inspection procedure is as follows:
1. Shut off the fan, but leave the pump running.
2. Remove the eliminators.
3. Check to see if the nozzles are producing the spray pattern shown
in Figure 8.
4. Clean any nozzles which are clogged. If necessary, the nozzle and
rubber grommet may be removed for cleaning.
5. Inspect the coil or wet deck surface. Any corrosion, damage, or
obstructions must be corrected.
NOTE: Do not use steam or high
pressure water to clean cooling
tower wet deck surface other
than steel.