What to do if the compressor of my Bacharach Refrigerant Recovery System 3600 Test Equipment will not start?
- JJason ReeseAug 1, 2025
If the compressor of your Bacharach Test Equipment won't start, first, ensure the unit is properly plugged into a 110-120 volt power source. Then, check if the circuit breaker has tripped and reset it if necessary. If the recovery cylinder has reached its 450 psi high-pressure limit, replace it with an empty one or cool it with water/ice. If the vacuum pressure switch has been activated, turn the unit off and apply 1-2 psig pressure to the inlet port to reset it. Also, remove any restrictions on the high side. If the thermal overload is bad, call Bacharach for service.