What to do if the Bartec SILAS A7-3741-1110 Control Unit does not operate?
- AAlyssa OconnorAug 9, 2025
If your Bartec Control Unit isn't operating and the display is blank, first, check the mains voltage supply cable to ensure it's properly connected and providing power. Also, verify that purging gas is connected. If the issue persists, and the electrical equipment was switched on without pre-purging, note that the purging time must count down. If none of these steps resolve the issue, it is possible that the device is defective and should be returned to the manufacturer for further inspection.