EasyManua.ls Logo

Basler BE1-851 - Generator Operational Protection; Reverse Power and Loss-of-Field Protection

Basler BE1-851
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
FIGURE 15. IMPEDANCE RELAY, LOOKING FOR
REMOTE LINE FAULTS.
Reverse Power Protection
The reverse-power relay (32) in Fig. 16 senses
real power flow into the generator, which will
occur if the generator loses its prime-mover
input. Since the generator is not faulted, CTs on
either side of the generator would provide the
same measured current.
FIGURE 16. ANTI-MOTORING (32), LOSS-OF-FIELD
(40), PROTECTION.
In a steam-turbine, the low pressure blades will
overheat with the lack of steam flow. Diesel and
gas-turbine units draw large amounts of motoring
power, with possible mechanical problems. In the
case of diesels, the hazard of a fire and/or
explosion may occur due to unburnt fuel. There-
fore, anti-motoring protection is recommended
whenever the unit may be connected to a source
of motoring power. Where a non-electrical type of
protection is in use, as may be the case with a
steam turbine unit, the 32 relay provides a
means of supervising this condition to prevent
opening the generator breaker before the prime
mover has shut down. Time delay should be set
for about 5-30 seconds, providing enough time
for the controls to pick up load upon synchroniz-
ing when the generator is initially slower than the
system.
Since motoring can occur during a large
reactive-power flow, the real power component
needs to be measured at low power factors. The
BE1-32R measures real power down to 0.1 pf.
The BE1-951, BE1-1051, and BE1-GPS measure
real power down to below 0.01 pf, depending on
current magnitude.
Fig. 17 shows the use of two reverse-power
relays: 32-1 and 32-2. The 32-1 relay supervises
the generator tripping of devices that can wait
until the unit begins to motor. Overspeeding on
large steam-turbine units can be prevented by
delaying main and field breaker tripping until
motoring occurs for non-electrical and selected
electrical conditions (e.g., loss-of-field and
overtemperature). Relay 32-1 should be delayed
maybe 3 seconds, while relay 32-2 should be
delayed by maybe 20 seconds. Time delay
would be based on generator response during
generator power swings. Relay 32-2 trips directly
for cases of motoring that were not initiated by
lockout relay 86NE — e.g., governor control
malfunction.
FIGURE 17. REVERSE-POWER RELAY 32-1 PREVENTS
LOAD REJECTION BEFORE PRIME MOVER
SHUTDOWN FOR SELECTED TRIPS; RELAY 32-2
OPERATES IF MOTORING IS NOT ACCOMPANIED BY
AN 86NE OPERATION.
Loss-of-Field Protection
Loss of excitation can, to some extent, be
sensed within the excitation system itself by

Related product manuals