EasyManua.ls Logo

Basler BE1-851 - Page 20

Basler BE1-851
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
FIGURE 32. SUGGESTED MINIMUM PROTECTION
EXAMPLE (HIGH-RESISTANCE GROUNDING).
The Basler BE1-951, BE1-1051, BE1-GPS100,
and BE1-59N include a third harmonic under-
voltage function (27-3N), that provides supervi-
sion of the grounding system, protects for faults
near the generator neutral, and detects a shorted
or open connection in the generator ground
connection or in the distribution transformer
secondary circuit.
FIGURE 33. EXTENDED PROTECTION EXAMPLE (HIGH-RESISTANCE GROUNDING).
Fig. 33 shows the application of additional relays
for extended protection: overexcitation relay (24),
negative sequence overcurrent and overvoltage
relay (46 and 47), ground-overcurrent relay
(51GN), voltage-balance relay (60), field-ground
relay (64F), frequency relay (81) and the 27/50/
62 relay combination for inadvertent energization
protection. Relay 51GN provides a second
means of detecting stator ground faults or faults
in the generator connections or faults in the delta
transformer windings. Differential relay 87T and
sudden-pressure relay 63 protect the unit step-up
transformer. Relay 51N provides backup for ex-
ternal ground faults and for faults in the high-
voltage transformer windings and leads. This
relay may also respond to an open phase con-
dition or a breaker-interrupter flashover that ener-
gizes the generator. The 51N relay will be very
slow for the flashover case, since it must be set
to coordinate with external relays and is a last-
resort backup for external faults.
Figure 33 shows wye-connected VTs, appropri-
ate with an isolated-phase bus.

Related product manuals