Operator's Manual Rev: D08
Environmental Conditions
The BECSys2 is housed in a NEMA 4X (IP65) enclosure. It should not be used in explosive environments. The
BECSys2 should be mounted so that adequate ventilation is provided around the enclosure, preventing general
environmental specifications from being exceeded (see table below).
Environmental Specifications
Specification Rating
Storage Temperature -30 to 60 Deg C
Ambient Operating Temperature -18 to 40 Deg C
Ambient Humidity 95% non condensing maximum humidity
Electrical Specifications
The BECSys2 may be ordered in either a 115VAC model or a 230VAC model. Following are the electrical specifications
for each model:
115VAC Model:
Voltage: 115VAC 60Hz
Phase: Single
Current: 9.25 Amps Full Load
(0.25 Amps – Controller)
(9 Amps – Relay Outputs, 3A X 3)
230VAC Model:
Voltage: 230VAC 50Hz
Phase: Single
Current: 9.125 Amps Full Load
(0.125 Amps – Controller)
(9 Amps – Relay Outputs, 3A X 3)