OperationOperation
EDS44x_D00201_07_M_XXDE/06.2020
35
9.3 Resetting saved alarm messages (RESET button)
If the fault memory is enabled, the alarm state will remain, even after the cause of the fault
has been eliminated, until a "RESET" is carried out.
A RESET is carried out in the following way:
• Press the "RESET" button on the front panel of the EDS44x-L twice (EDS44x-L only)
• Press an external RESET button connected to the EDS44x-x
• Send a RESET command via the BS bus (EDS44x-x)
Saved alarm messages that are no longer pending are deleted, the alarm relay is de-en-
ergised, the alarm LEDs go out and no alarm messages remain on the BS bus.
9.4 Deactivating the buzzer and resetting the fault message
• Press the RESET button on the EDS44x-L to mute the buzzer for the present alarm
message.
• To reset a fault message, press the RESET button again.
The buzzer functions can be assigned in the device menu of the ISOMETER®. For further
information, refer to "Digital outputs of the EDS44x-L" on page 38 or to the manual of the
ISOMETER®.
9.5 Running a test (TEST button)
A test can be carried out to check the device function of the EDS. There are several ways
to start a test:
EDS44x-L:
• Select standard display on the ISOMETER® and then press the "TEST" button on the
front panel of the EDS44x-L.
• Press an external TEST button connected to the digital input
• Send TEST command via BS bus or Modbus RTU.
EDS44x-L and …-S:
• Press TEST button on the ISOMETER®.
The EDS44x-L responds as follows:
• "ALARM I
L
" LED and "ALARM I
n
" LED light up.
• All alarm relays switch (function can be deactivated).
• An alarm message is sent on the BS bus.
• An entry with the suffix "TEST" is stored in the history memory of the ISOMETER®.
• All active channel LEDs light up.
After finishing the test, all LEDs must go out again, except the "ON" LED.