6 LG_D00393_00_Q_XXEN / 05.2019
LifeGuard® Series
Use - Enclosure Front
Apply Power
To apply power, close the customer-supplied circuit breaker / disconnect on the line side of
the LifeGuard panel. If there are no ground faults present on the system, the green POWER
ON LED will light.
Perform Test (Trip Level Options A and F)
To perform a test on models with trip level option A or F, follow the instructions below.
Push TEST for at least two (2) seconds.
The unit will trip, the green POWER ON LED will go out, and the red CIRCUIT TRIPPED LED
will illuminate. Power to any connected loads will be interrupted.
An internal self-test will initiate, taking approximately ten (10) seconds.
Push RESET for at least one (1) second.
If the internal self-test has completed, the unit will reset, the red CIRCUIT TRIPPED LED
will go out, and the green POWER ON LED will illuminate. Power will be restored to the
load.
Perform Test (Trip Level Options D and E)
To perform a test on models with trip level option D or E, follow the instructions below.
Push TEST for at least two (2) seconds.
The unit will trip, the green POWER ON LED will go out, and the red CIRCUIT TRIPPED LED
will illuminate. Power to any connected loads will be interrupted.
Push RESET button for at least one (1) second.
The unit will reset, the red CIRCUIT TRIPPED LED will go out, and the green POWER ON
LED will illuminate. Power will be restored to the load.
Field Adjustment, Error Codes and troubleshooting
Refer to LifeGuard user manual.
red
POWER LED / RESET button:
Illuminates when the panel has powerd and the
device has not tripped /
RESET button: Resets the panel if faults have been
cleared (momentary push).
green
TRIPPED LED / TEST button:
Illuminates when tripped /
TEST button: Performs a functional test
(hold for at least 2 seconds).
dashed
Emergency-stop button (OPTION “S” ONLY):
Pushing this button will disallow a start regard-
less of ground fault condition. Once pushed in it
needs to be pulled out and twisted for the panel
to resume normal function. This is only included in
models which end in “-S”
POWER
ON
Push to Reset
CIRCUIT
TRIPPED
Push to Test
OPERATION
The green POWER ON lamp
illuminates when power is available to the
load.
The red CIRCUIT TRIPPED lamp illumi-
nates when power is removed from the
load..
If the unit trips, clear the fault and press
Reset to resume operation.
TESTING Unit must be tested at least
once per month
Press Test for > 2 seconds.
Unit must trip.
Press Reset for > 1 second.
Unit should reset, restoring power to
the load.