CTUB100-series_D00362_06_M_XXEN/04.2025 7
LINETRAXX® CTUB100 series
CTBC35P ....................................................................160 A / 160 A
CTBC60 at I
Δn
≥ 30 mA ..............................................200 A / 160 A
CTBC60 at I
Δn
≥ 300 mA ............................................400 A / 250 A
CTBC60P ....................................................................400 A
/ 320 A
CTBC120 at I
Δn
≥ 100 mA ..........................................400 A / 330 A
CTBC120P at I
Δn
≥ 100 mA ........................................630 A / 630 A
CTBC210 at I
Δn
≥ 300 mA ..........................................630 A / 630 A
CTBC210P at I
Δn
≥ 100 mA ........................................630 A / 630 A
CTBC210P at I
Δn
≥ 300 mA ....................................1000 A / 1000 A
Measurement accuracy ................................. ±1 % of full scale value
Test winding ................................................................................. yes
Rated continuous thermal current
1)
I
cth
..................................... 125 A
at UL applications ............................................................30 A
Rated short-time thermal current
1)
I
th
................................2.4 kA/1 s
Rated dynamic current
1)
I
dyn
.............................................6 kA/40 ms
1)
refers to the residual current
i
Residual current > 6 kA: Device defect CTUB1…, message via LED
There is no danger of fire or electric shock..
Possible response values (set on the evaluator)
CTBC20, CTBC20P .................................................... 10 mA…500 mA
CTBC35, CTBC35P, CTBC60, CTBC60P ............................ 30 mA…10 A
CTBC120, CTBC120P, CTBC210P ................................. 100 mA…10 A
CTBC210 ..................................................................... 300 mA…10 A
Measuring ranges CTUB101, CTUB102
Measuring range 1 (I
∆n
≤ 0.1 A) .......................... 0…900 mA (peak)
Measuring range 2 (0.1 A < I
∆n
≤ 0.5 A).................. 0…3.5 A (peak)
Measuring range 3 (I
∆n
> 0.5 A) ............................... 0…20 A (peak)
Measuring range CTUB105
Measuring 3 (I
Δn
> 0.5 A) ......................................... 0…20 A (peak)
Indication
Multicolour LED ........................................................... See pages 3/4
Output
Name .............................................................................. S1 (k), S2 (l)
Scaling ............................................................................. 400 mV/1 A
Max. voltage .............................................................................±10 V
Output device error
CTUB101, 102 .........................................Max. full scale value
CTUB105 ............................................................................8 A
Max. connector length ................................................................10 m
Output resistance ..................................................................... 172 Ω
Input
Name ................................................................ T (for CTUB101 only)
Current load .......................................................................< 300 mA
Environment/EMC
EMC ................................................................................ IEC 62020-1
Operating temperature ................................................... -25…70 °C
Classification of climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ..................................................3K22
Transport (IEC 60721-3-2) ..........................................................2K11
Long-term storage (IEC 60721-3-1) ...........................................1K22
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ..................................................3M11
Transport (IEC 60721-3-2) .......................................................... 2M4
Long-term storage (IEC 60721-3-1) ......................................... 1M12
Connection
Max. connection length ..............................................................10 m
Connecting cables are optionally available.
Use 60/75 °C copper lines only.
Terminal block
Manufacturer ........................................................... Phoenix Contact
Type ................................................................DFMC 1.5/4-ST-3.5 BK
The connection conditions of the manufacturer apply.
Connection properties
rigid .............................................. 0.2…1.5 mm² (AWG 24…16)
flexible ................................................................... 0.2…1.5 mm²
with ferrule ....................................................... 0.25…0.75 mm²
Mounting CTBC…
Screw type
CTBC20…60(P) ........................................... DIN EN ISO 7045 - M5
CTBC120…210(P) ....................................... DIN EN ISO 7045 - M6
Washer type
CTBC20…60(P) ..................................... DIN EN ISO 7089/7090 - 5
CTBC120…210(P) ................................ DIN EN ISO 7089/7090 - 6
Tightening torque
CTBC20…35 (P) ................................................................. 0.6 Nm
CTBC60…210(P) .................................................................. 1 Nm
Other
Operating mode ...............................................Continuous operation
Mounting ...................................................................... Any position
Degree of protection, built-in components (DIN EN 60529) .........IP40
Degree of protection, terminals (DIN EN 60529) .......................... IP20
Flammability class .............................................................. UL94 V-0
Software ....................................................................................D591
Weight
CTUB10x-CTBC20 ..............................................................≤ 230 g
CTUB10x-CTBC20P ............................................................. ≤ 290 g
CTUB10x-CTBC35 ............................................................... ≤ 310 g
CTUB10x-CTBC35P ............................................................. ≤ 390 g
CTUB10x-CTBC60 ............................................................... ≤ 530 g
CTUB10x-CTBC60P ............................................................. ≤ 690 g
CTUB10x-CTBC120 ......................................................... ≤ 1460 g
CTUB10x-CTBC120P ........................................................ ≤ 1820 g
CTUB10x-CTBC210 .......................................................... ≤ 4290 g
CTUB10x-CTBC210P ........................................................ ≤ 4940 g
The use of the power supply units listed at “Accessories” is
recommended. The use of a surge protection device is mandatory
for these power supply units.