13.3) PARAMETERS, LOGICS AND SPECIAL FUNCTIONS
The following tables describe the functions available on the control unit
13.3.1) INSTALLATION (INST)
MENU FUNCTION MIN-MAX-(Default) MEMO
BOOM
Select the length of the boom installed on the barrier.
Value expressed in meter from 3m to 5m (EVA5) or from 7m to 8m (EVA7)
According to the selected boom length, the optimal value of speed will be set.
3/5 -7/8 (3-5)
Pos
Set the closing direction of the barrier (see fig. 3)
The symbol 0--- indicates right barrier (R/RIGHT) DEFAULT
The symbol ---0 indicates left barrier (L/LEFT)
Verify the opening direction of the boom and in case reverse it. Every change of this func-
tion automatically implies the starting of a new AUTOSET procedure.
0--- = RIGHT
---0 = LEFT
( RIGHT )
Mode
Select the use mode of the barrier.
Norm: Standard operating mode, for barriers used in a residential/industrial environment and
with normal traffic.
Parc: Park operating mode, for barriers used in parking systems. In this mode, to promote
transit of a high number of vehicles, the control unit automatically sets a specific configuration
which includes:
1) Rapid closure enabled (SCL:ON) with time reduced from 3 to 0 seconds.
2) Automatic closure enabled (TCA:ON) which with rapid closure enabled causes, during the
opening phase, immediate closure of the barrier as soon as the PHOT input is free.
3) During the closure phase, PHOT entrance activation stops the barrier, as soon as the PHOT
input is free again, the barrier starts the closure manoeuvre.
Norm - Parc (Norm)
13.3.2) PARAMETERS (PAR)
MENU FUNCTION MIN-MAX-(Default) MEMO
TCA
Automatic closing time. Enabled only with logic “TCA”=ON.
At the end of the set time, the control unit commands a closing maneuver .
1-240-(20s)
FSTS
Adjusts the opening and closing speed of the barrier (standard speed, before the slowdown phase).
50-99-(99)
sldo
Adjusts the slowdown speed of the barrier during the opening phase* (Fig.10 -slow Open). 20-70-(50)
sldc
Adjusts the slowdown speed of the barrier during the closing phase * (Fig.11 -slow Close). 20-70-(50)
tsmo
Sets the starting point of the slowdown during the opening phase (Fig.10 - beginning of the slow
Open). The value is expressed in percentage on the entire stroke.
1-99-(20)
tsmc
Sets the starting point of the slowdown during the closing phase (Fig.11- beginning of the slow
Close). The value is expressed in percentage on the entire stroke.
1-99-(20)
PMO
Adjusts the motor torque applied to the barrier during the opening phase.* 1-99-(20)
PMC
Adjusts the motor torque applied to the barrier during the closing phase.* 1-99-(20)
PSO
Adjusts the motor torque applied to the barrier during the slowdown in opening phase * (Fig.10
- Slow Open).
1-99-(20)
PSC
Adjusts the motor torque applied to the barrier during the slowdown in closing phase * (Fig.11
- Slow Close).
1-99-(20)
SeaU
Adjusts the intervention threshold of the anti crushing device (Encoder) during the normal speed*.
0:Off -1: minimum sensitivity - 99: maximum sensitivity
0-99-(0%)
SEAR
Adjusts the intervention threshold of the anti crushing device (Encoder) during the slowdown speed*.
0:Off -1: minimum sensitivity - 99: maximum sensitivity
0-99-(0%)
tls
Activation time of the courtesy light contact. Value expressed in seconds. At the beginning of
each maneuver the contact latches for the set time.
See the description of AUX1 parameter.
1-240 (60)
saso
Sets a short reversion after reaching the limit switch in open position. Can be useful for facilitat-
ing the manual release.
0-5 (0)
sasc
Sets a short reversion after reaching the limit switch in close position. Can be useful for facilitat-
ing the manual release.
0-5 (0)
aux1
Selects the functioning mode of the auxiliary output 1 (N.O. clean contact)
0: Open barrier light, close contact when the barrier is open, open contact when the barrier is
close, intermittent during the maneuver (fig. 15, SCA)
1: Second radio cannel of the built in receiver
2:
Boom light, for controlling the LED light installed on the BOOM (EVA.LED), see also the parameter LBAR.
3: Courtesy light, the contact remains close according to the parameter TLS (fig.15 SERVICE LIGHT)
4: Photocells test, see wiring diagram in Fig.15 (PHOTOTEST)
5: Close contact with open barrier
6: Close contact with close barrier
7: Maintenance warning light. The contact closes when the number of manoeuvres set in the
Maintenance Cycle menu is reached (MACI).
0-6-(0)