7.4.3 and button
Lock / Unlock the display:
Hold and for 5 seconds to lock/unlock the display.
Water temperature setting:
Press or to set the water temperature directly.
Parameter checking:
Press first, then press to check the User parameter from d0 to d11
Code
Condition
Scope
Remark
d0
IPM mould temperature
0-120
Real testing value
d1
Inlet water temp.
-9℃~99
Real testing value
d2
Outlet water temp.
-9℃~99
Real testing value
d3
Ambient temp.
-30℃~70
Real testing value
d4
Frequency limitation code
0,1,2,4,8,16
Real testing value
d5
Piping temp.
-30℃~70
Real testing value
d6
Gas Dischargetemperature
0℃~C5 (125)
Real testing value
d7
Step of EEV
099
N*5
d8
Compressor running frequency
099Hz
Real testing value
d9
Compressor current
030A
Real testing value
d10
Current fan speed
0-1200 rpm
Real testing value
d11
Error code for last time
All error code
Remark: d4: Frequency limitation code, 0: No frequency limit,
1: Coil pipe temperature limit, 2: Overheating or overcooling frequency limit,
4: Drive Current frequency limit, 8: Drive voltage frequency limit,
16: Drive high temperature frequency limit.