5.5.4 Description of ‘read configuration’ menu ( )
- To entrer Read Configuration menu, move in the main menu like described in chapter 5.5.2 and
press OK (Stop) when
is displayed.
- Go UP and DOWN to reach the sub-menus
- Press OK to enter the sub-menus
- Read the setting of the local command.
- Read the setting of the proportional command.
If proportional command is ON, press OK to read the type of input signal.
If the selected input signal is 4/20, press OK in order to read the failsafe position.
You can return to the upper menu by pressing Esc. (Escape).
- Read the nominal voltage (Single phase or 24VDC) or (3-phase)
- Read the closing direction (Close clockwise) or (Close Counter- ClockWise)
5.5.5 Read the existing alarm codes ( )
- To enter the Read Error menu, move in the main menu like described in chapter 5.5.2 and press
OK (Stop) when
is displayed.
- Go UP and DOWN to read the codes
- If there’s no alarm, display is
Code Alarm Condition
--- No fault found
E01 Max torque reached Not available on EZ4 à EZ15
E02 Thermal overload
E03 Loss of one phase For 3-phase supply
E04 Loss of 4/20mA input signal Not applicable with 0/20mA
E05 Rotor is jammed
E06 Position sensor in fault
E07 Torque sensor in fault Not available on EZ4 to EZ15