SPECIFICATIONS
Voltage ................................................................ 120V/277VAC, 60Hz
Load capacity ............................................................ 120V 300W LED
800W/VA@120V fluorescent lamp Rapid Start
1200W/VA@277V fluorescent lamp Rapid Start
HP Rating ................................................................................... 1/6HP
Time Delay Adjustment ...........................................15 secs to 30 mins
Operating Temperature ................................ 32° to 131°F (0° to 55°C)
Operation humidity range...............................95%RH,non-condensing
Coverage range ............................................................... 180 Degrees
COVERAGE AREA
BESTTEN
Power for Today, Ideas for Tomorrow
DESCRIPTION
OPERATION
For sensor to operate, the ON/OFF switch
MUST
be manually pushed
one time after installation or a power outage.
VAC
When the button is pressed Manual ON, Auto OFF
OCC When the button is released
Auto ON, Auto OFF
with Auto set mode*
*Auto Set Mode
If the switch is turned OFF manually, automatic-ON is re-enabled when no
motion is detected for 1 minute. This prevents the switch from turning ON
after it was deliberately turned OFF.
Windows, glass doors, and other transparent barriers
will obstruct the sensor’s view and prevent detection.
Note: The coverage area data is measured under the best temperature condition
(20-25℃), and a higher temperature may not lead to an ideal coverage area.
1. To avoid overheating and possible damage to this device and other equipment, DO NOT
install to control a receptacle.
2. To be installed and/or used in accordance with appropriate electrical codes and regulations.
3. Use this device with copper or copper clad wire only.
4. The neutral wire is required. If no neutral is available, consult an electrician
5. The sensor switch requires an unobstructed view of room occupants to detect motion.
6. Hot objects or moving air currents can affect the performance of the sensing switch.
7. For indoor use only. Operate between 32° to 131°F (0° to 55°C).
8. Clean the sensor with a soft damp cloth only. DO NOT use any chemical cleaners.
9. If you are unsure about any part of these instructions, consult an electrician.
10. Wiring Diagram or equivalent giving the electrical rating and illustratinghow connections
to the supply circuit are to be made.
11. The device is to be used in conjunction with a UL Listed Cover Plate.
12. Intended for use with eletronic ballast, Type ICN-4S54-90C-2LS-G, manufactured by
Philips Lighting Electronics N A.
13. For supply connections use 18AWG or larger wires suitable for at least 75°C
1. The sensor switch turns lights or fans ON and OFF based on
occupancy/vacancy and ambient light level.
2. The sensor uses passive infrared technology to sense human
motion and defines it as occupancy. A green LED indicator on the
control panel blinks upon occupancy and then resets.
3. The sensor turns on automatically when it detects occupancy. Once
the space is vacant and the time delay elapses, it turns off automati-
cally.
4. Occupancy sensor can be converted to vacancy sensor.
5. If adequate ambient light is already present in the area, the sensor
will remain OFF. When the light drops below a set level and the sensor
detects occupancy, the sensor turns on. The light sensor can be
bypassed by setting the light sensitivity dial.
6. Once turned on, the switch remains ON until the space is vacant, or
the ambient light rises above the setpoint and the time delay expires.
The sensor responds to temperature changes so DO NOT mount it
directly above a heat source in a location where hot or cold drafts
will blow directly on it, or where an unintended motion (e.g., hallway
traffic) is within the sensor’s field-of-view.
LOCATION / MOUNTING
COVERAGE PATTERNS: The sensor detects motions in areas up to
720 sq. ft. and up to 30 feet from the sensor. The Fresnel lens on the
sensor is a multiple segment viewing lens with a field of view of 180.
The sensor must have a clear view of the people in the space in order
to detect occupancy. Obstructions, such as furniture blocking the
sensor’s lens may prevent occupancy detection.
Floor
Side View
4.0’
(1.2m)
6.0’
(2.0m)
30’
(9.1m)
Top View
12’
(3.7m)
30’
(9.1m)
120V 300W LED, 800W/VA @120V fluorescent lamp Rapid Start, 1200W/VA @277V fluorescent lamp Rapid Start