Each component has the following functions:
It is shown below:
Turns on the appliance and puts on standby. The fan starts up after a
few moments and then the compressor starts up (if necessary). The
button is backlit when the equipment is in use.
Advises that the tank is full: the LED of the button flashes.
Once the tank is emptied and re-inserted correctly in its seat, the
defrost
During dehumidification, the defrost function is activated based on
the ambient temperature (T.A.):
- With T.A. 24 °C or greater, defrost is not activated.
- With T.A. between 18 °C and 23 °C, defrost is activated every 2 h
and lasts for 5 min.
- With T.A. between 12 °C and 17 °C, defrost is activated every 25
min and lasts for 5 min.
- With T.A. between 5 °C and 11 °C, defrost is activated every 20 min
and lasts for 5 min.
NOTE: - Do not turn off or disconnect the power cable during
defrost. - During defrost, dehumidification and air can be
intermittent.