EasyManua.ls Logo

Bindicator Pulse Point II Series - Page 19

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
www.bindicator.com
LVP180914 Rev. D
FAILSAFE SELECTION
The LP II is factory set for high level fail-safe operation. The Fail-Safe is controlled by SW1, position 1 on Standard units;
SW5, position 1 for Advanced units. Refer to Figure 13 to determine the Fail-Safe mode that suits your application.
Figure 13. Fail-Safe Operation
HIGH LEVEL FAILSAFE OPERATION DEFAULT
DIP Switch Settings
STANDARD: SW1-1 is OFF
ADVANCED: SW5-1 is OFF
Alarm State (material above the rod)
Main Relay is de-energized
Relay NC contacts are closed
Relay NO contacts are open
Alarm LED is ON
Non-Alarm State (material below the rod)
Main Relay is energized
Relay NC contacts are open
Relay NO contacts are closed
Alarm LED is OFF
Note: If the electrical power fails, the main relay turns OFF, giving the same indication
as if material is above the rod.
LOW LEVEL FAILSAFE OPERATION
DIP Switch Settings
STANDARD: SW1-1 is ON
ADVANCED: SW5-1 is ON
Alarm State (material below the rod)
Main Relay is de-energized
Relay NC contacts are closed
Relay NO contacts are open
Alarm LED is ON
Non-Alarm State (material above the rod)
Main Relay is energized
Relay NC contacts are open
Relay NO contacts are closed
Alarm LED is OFF
Note: If the electrical power fails, the main relay turns OFF, giving the same indication
as if material is below the rod.