SIGNAL-20M
INTRUSION AND FIRE ALARM CONTROL PANEL
Operation Manual
ISO 9001
1 GENERAL INFORMATION
1.1 The Signal-20M Intrusion and Fire Alarm Panel (hereinafter referred to as Panel) is intended for use as a combined device to
monitor and control alarms in the following systems:
Fire alarm and extinguishing systems
Evacuation and alarm system of Type 1 and Type 2
Intrusion detection and panic alarm system
Auxiliary alarm systems
1.2 The Signal-20M supports conventional (nonaddressable) threshold wire-connected detectors.
1.3 The Signal-20M can operate as a processing module of rate-of-rise heat detectors and supports sensing elements (thermal cables)
detecting temperature threshold exceedance.
1.4 The Signal-20M automatically monitors communication lines with detectors, call points and actuating devices of fire protection
systems.
1.5 The panel is not a scalable system.
1.6 The panel supports connection to PC for control and programming functions.
1.7 The panel is designed for 24\7 continuous operation
1.8 The panel is a reparable device with periodic maintenance
1.9 The Panel is not designed for the use in aggressive, dust, explosive and fire-hazardous environments.
2 SPECIFICATIONS
Table 2.1 Panel specifications
No
Description
Value
2.1
DC supply voltage, V
10.2 … 28.0
2.2
Consumption current, mA, no more *
- in ‘Quiescent mode
- in ‘Fire’ mode
* excluding current consumption of alarm devices
400
650
2.3
Power inputs
2
2.4
Startup time, s
5
2.5
Inputs
20
2.6
Voltage on unloaded input terminals, V
26.5 … 27.5
2.7
Input short-circuit current limitation, not more than, mA
26.5
2.8
Resistance of input terminal resistor,
4.7±5 %
2.9
Max. current consumption of all detectors in standby mode, mA
- Type 1 (Fire smoke) inputs
- Type 2 (Fire combined) inputs
3.0
1.2
2.10
Input resistance in various states
See Table 2.2
2.11
Maximum allowable resistance of the sensing element of a linear heat detector (thermal
cable),
1.5
2.12
Input communication line:
- max. wire resistance (excluding terminal resistor), Ω
- insulation resistance of wires, not less, mΩ
100
50
2.13
Input voltage reset time, s
3,0
2.14
Number of outputs:
- non-monitored, ‘dry contact’ (130 VAC / 170VDC, 0.1 A)
- monitored (10.2 ... 28.0 V, 2.5 A)
3
4
2.15
Rated load current of monitored output, mA
5 … 2500
2.16
Output terminal resistance,
4.7±5 %
2.17
Voltage (negative) on inactive output with the connected terminal resistor, mV
- 1100 - 2200
2.18
Output line health check current (reverse), no more, mA
- 1.5
2.19
Ingress protection according to GOST 14254-2015
IP40
2.20
Mechanical tolerance according to OST 25 1099-83
Placement category 3