Troubleshooting
Display Cause Solution
E9 Temperature limiter opened circuit
(overheat). Trips at 220F (104C).
Check connections.*
Check heat exchanger condition.*
EA No ionization during safety time (safety time
out).
Check gas pressure.*
Check that gas is not diluted with air, as a result
from recent gas pipeline rework.*.
Check if vent terminal is blocked (especially when
the appliance starts up for some seconds and then
looses ionization signal).*
Check ionization electrode.*
Check for a proper ground.*
EC The ionization signal momentarily
disappeared more then 3 times in less then
30 seconds.
FA Leakage error (gas valves do not close gas
circuit).
Check gas valve and control unit.*
F7 Ionization error (flame sensing at stand-by). Check control unit.*
E0 Internal software/hardware failure. Check control unit.*
A7 Hot water temperature sensor/receiver
defect (from control unit).
Check water temperature sensor/receiver and
connections.*
Check room area temperature where heater is
located, it must be above 36°F (2°C)
A9 Hot water temperature sensor/receiver mis-
assembled (from control unit).
Check that the water temperature sensor/receiver is
properly assembled in the water pipe.*
Check if vent terminal is blocked or if vent terminal is
according with
chapter 2.9
.*
In case of high altitude installation confirm that
necessary adjustment steps have been taken.*
C1 FAN rotation too low at start-up (from
control unit).
Check supply voltage.*
Check fan and connections.*
Check control unit.*
Check if vent terminal is blocked or if vent terminal is
according with
chapter 2.9
. *
Check CO
2
levels (see chapter
9
).*
C6 FAN rotation too low at operation (from
control unit).
Check supply voltage.*
Check fan and connections.*
Check control unit.*
Check if vent terminal is according with
chapter 2.9
.*
C7 No rotational speed sensor signal from FAN Check fan and connections.*
Check control unit.*
Check CO
2
levels (see chapter
9
).*
CA Water flow signal over specified maximum
value
Check water valve and flow sensor.*
E2 Inlet temperature sensor fault Check water temperature sensor/receiver and
connections.*
Check room area temperature where heater is
located, it must be above 36°F (2°C)
A2 Overheat protection fault Check connections to the overheat protection.*
Check sensor continuity.*
Check heat exchanger sealings and walls.*
Table 5
* By installer or service technician only.