Recommended exhaust vent terminator position
Fig. 16
* Subject to local codes and anticipated snow level
** Other equipment that operates with a mechanical air inlet may require greater distances, reference manufacturer's instructions
Ref. Description Minimum distance
A
Directly below an opening; operable windows, doors and any non-
mechanical fresh air openings
36 in
B
Below a gutter, sanitary pipework or eaves 24 in
Below a gutter, sanitary pipework or eaves, protected by metal
shielding
12 in
C From any internal corner 12 in
D*
Above ground 12 in
Above a paved sidewalk 7 ft
E
From an opposing wall or structure facing the termination 24 in
From any other building opening, gas utility meter, service regulator
or the like
36 in
F From a terminator facing a terminator 48 in
G Vertically between two exhaust vent terminators on the same wall 60 in
H Horizontally between two exhaust vent terminators on the same wall 12 in
I**
Horizontally from combustion air inlet of 250 SX
36 in
Vertically above or below combustion air inlet of 250 SX
From the combustion air inlet of any other equipment 6 ft
J From any external corner 12 in
K
Horizontally from an opening; operable windows, doors and any
non-mechanical fresh air openings
12 in
L
Vertically from a wall, roof slope, or obstruction (venting through a
flat or pitched roof)
see ABOVE THE ROOF
requirements on following page
Table 4