EasyManua.ls Logo

Bosch AquaStar 250SX NG - Page 33

Bosch AquaStar 250SX NG
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 720 607 057
Special adjustment for measuring and adjusting CO2 levels
33
D. Returning to Service:
1. Return slotted cover to original position.
2. Reinstall Torx cover.
3. Remove CO
2
analyzer probe and reinstall flathead
screw in exhaust collar.
4. Turn ON/OFF switch to the OFF (O) position and
then back to the ON (I) position.
5. Heater is ready for normal operation.
Final Readings
P2 CO
2
Reading: % CO
2
P1 CO
2
Reading: % CO
2
Fig. 44
Fig. 45
Without Front
Cover
With Front
Cover
Nat. Gas Nat. Gas
max. input P1 9.1 ± 0.1 % 9.7 ± 0.1 %
min. input P2 9.4 ± 0.1 % 9.7 ± 0.1 %
LP Gas LP Gas
max. input P1 10.1 ± 0.1 % 10.7 ± 0.1 %
min. input P2 10.4 ± 0.1 % 10.7 ± 0.1 %
* Final reading must be confirmed with the front cover
on, CO
2
levels increase when the cover is installed.
Table 9

Related product manuals