Aspiration smoke detector LSN improved Technical specifications | en 15
Bosch Sicherheitssysteme GmbH Operation guide 2020.04 | 6.1 | F.01U.029.275
Notice!
Only type DM‑TT‑50(80), DM‑TT‑10(25) and DM‑TT‑01(05) detector modules with VdS
certification can be used in the standard units from the FAS-420 series. The detector modules
must be ordered separately.
Information on other accessories for special applications can be found in
FAS‑ASD‑DIAG Diagnostic Software, page 17
Remote Indicators, page 17
Device Mounting, page 18
Ceiling lead-through, page 21
Water Separator for Humid Areas
Detonation safety barrier for potentially explosive areas, page 24
.
3.5.2 FAS‑420 Connections
1
2
3
1
4
5
FAS -420 series
FAS -420 series
FAS / FCS
Figure3.1: FAS-420 connections (see table on next page for explanations)
Position in
figure
Function Explanation
FAS-420 series 1 Cable bushing for connection of fire panel
and additional power supply (input/
output)
1 x M20, for cable diameters of
8-12mm
2 Pipe system 1 connection For Ø 25mm pipe system
3 Pipe system 2 connection (only for devices
with a two pipe system)
For Ø 25mm pipe system
4 Connection for air-return pipe
5 Cable bushing for connection of fire panel
and additional power supply (input/
output)
2 x M25 for cable diameters of
9-14mm (expandable to 14-
18mm)

Table of Contents