Go/No-Go testing can be used to confirm a detector is within its sensitivity limits and operating normally
GO/NO-GO TESTING FCP-350-P/FCP-350-PTH
1. Place the Test Magnet to align the LED marking as shown.
2. For go: The detector will blink red every second. Holding the
magnet in position for at least 13 seconds will cause the
detector to alarm with the red LED latched on.
For no-go: After at least 13 seconds, the detector will continue
to blink red every 3 seconds and never alarm or latch red.
3. Upon reset, the smoke detector LED should blink Green every
3 seconds. If the detector blinks red, it should be replaced.