Permissible air speed 20 m/s
Permissible operating temperature
– FCP-OC320 -10 °C to +50 °C
– FCP-OT320/FCH-T320 -20 °C to +50 °C
– FCP-O320 -20 °C to +65 °C
Monitoring area
– FCP-OC320, FCP-OT320, FCP-O320
Max. 120 m
2
(Heed local guidelines!)
– FCH-T320
Max. 40 m
2
(Heed local guidelines!)
Maximum installation height 16 m (Heed local guidelines!)
– FCP-OC320, FCP-OT320, FCP-O320 16 m (Heed local guidelines!)
– FCH-T320 6 m (Heed local guidelines!)
Response sensitivity
– Optical part < 0.2 dB/m, in line with EN 54 T7
– Thermal maximum part >54 °C
– Thermal rate-of-rise part (in line with EN 54‑5) FCH-T320: A2R
– Chemical part In ppm range
Storage
Maximum storage time 2 years
NOTE: Due to the characteristics of CO detecting components, the maximum storage time for devices with CO
sensor is 0,5 years.
Disposal
The device including the accessories and packaging shall be sorted for environmental-friendly recycling. Do not
dispose of power supplies into household waste. Please follow your local regulations on appropriate disposal.
Delivery and Selling
– The product may only be transported in its original packaging.
– Handle with care and avoid hits and shocks.
– Absolutely avoid damaging of the packaging or the product itself.
– Avoid extreme temperatures during transport.
– Not for sale to private persons but to trained and experienced persons only.
1.4 Troubleshooting
In case the product doesn’t work as expected go to the diagnostic menu of the connected panel controller and
take measures according to the shown error code. In the event of a defect, the entire product must be exchanged.
Refer to your local Bosch contact.
1.5 Restrictions of usage