Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
50
Cooler Operation
(cont.)
N-E5 Electronic Control Module Operation
(cont.)
Service Checks
N-E5 not operating:
Check for power supply to into the unit at the power point and Active - Neutral
incoming supply terminals.
Check if the N-E5 power indicator LED is illuminated.
Check the N-E5 is correctly located in the base terminal connector and mounting
bracket.
Check the N-E5 is set to the correct Network ID number.
Check if the N-E5 internal 8 Amp fuse is in circuit or is open circuit.
If fuse NOT open circuit:
Check the Servoseal / Drain valve wiring loom, motor and switch
mechanisms for short circuit.
If fuse IS open circuit (blown):
Check the pump motor and wiring loom for short circuit.
Check the water inlet solenoid and wiring loom for short circuit.
Check the fan motor and wiring loom for short circuit.
Replace 8 Amp fuse and re test.