ELECTRICAL DATA (cont)
FAN COIL UNITS
INDOOR
UNIT
619E
V (Single-
Ph, 60 Hz)
OPERATING VOLTAGE* FAN
Minimum Maximum FLA
009† 115 104 127
012† 208/230 187 253
009** 115 104 127
012** 208/230 187 253
018†
208/230 187 253 0.53
024†
018**
024**
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning, Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC Section 430-24
NEC National Electrical Code
RLA Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Cooling only fan coil unit.
**Heat pump fan coil unit.
NOTES:
1. The 018, 024, 048 outdoor units contain a 24-v transformer; addi-
tional transformers are not required. The 009, 012 outdoor units use
230-v (high voltage) controls.
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
4. Motor RLA values are established in accordance with UL (Underwrit-
ers’ Laboratories) Standard 1995.
16