EasyManuals Logo

Bryant 619E User Manual

Bryant 619E
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
ELECTRICAL DATA (cont)
FAN COIL UNITS
INDOOR
UNIT
619E
V (Single-
Ph, 60 Hz)
OPERATING VOLTAGE* FAN
Minimum Maximum FLA
009† 115 104 127
012† 208/230 187 253
009** 115 104 127
012** 208/230 187 253
018†
208/230 187 253 0.53
024†
018**
024**
LEGEND
FLA Full Load Amps
HACR Heating, Air Conditioning, Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC Section 430-24
NEC National Electrical Code
RLA Rated Load Amps (Compressor)
*Permissible limits of the voltage range at which unit will operate
satisfactorily.
†Cooling only fan coil unit.
**Heat pump fan coil unit.
NOTES:
1. The 018, 024, 048 outdoor units contain a 24-v transformer; addi-
tional transformers are not required. The 009, 012 outdoor units use
230-v (high voltage) controls.
2. All motors and compressors contain internal overload protection.
3. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
4. Motor RLA values are established in accordance with UL (Underwrit-
ers’ Laboratories) Standard 1995.
16

Other manuals for Bryant 619E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 619E and is the answer not in the manual?

Bryant 619E Specifications

General IconGeneral
BrandBryant
Model619E
CategoryAir Conditioner
LanguageEnglish

Related product manuals