EasyManua.ls Logo

CALEFFI Z-one ZSR10X Series - Page 13

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
1
2
3
L
POWER IN
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
N
L
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
R
W
T T COM
COMMS
D
P
ZONE 1
E / S
X X
T-STAT 3
C
R
W
T T COM
T-STAT 1
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
AUX
ON
OFF
ON
OFF
VALVE
OPEN
1
2
3
4
52
2 1 3
4 1 3
White Rogers
1361
Zone Valve
4 wire
Zone Valve
2 wire
Taco
570
2
Wiring a standard zone valve to Calef Z-one Relay
Since a two wire actuator does not have an end switch for feedback
to the ZVR control, the end switch terminals must have a jumper to
simulate the end switch. If the end switch jumper is not installed, no
demand will be sent to the boiler and the pumps will not turn on
.
Wiring a Taco 570 valve to Calef Z-one Relay
When connecting the Taco 570 zone valve to the Caleffi Z-one Relay,
the wiring of this valve can only be done in one way. The left motor
terminal on the ZVR series control must be connected to terminal 2
on the zone valve. The right motor terminal must be connected to
terminal 1 on the zone valve. Lastly, the left end switch terminal
must be connected to terminal 3 on the zone valve. Failure to follow
schematic will lead to damage of product.
Wiring a White Rogers 1361 valve to Calef Z-one Relay
The White Rogers 1361 zone valve requires 24 VAC to terminal 2
at all times, therefor connect to the R terminal of the associated
T-STAT on the ZVR control. The left motor terminal on the ZVR
series control must be connected to terminal 4 on the zone valve.
The right motor terminal must be connected to terminal 1 on the
zone valve. Lastly, the left end switch terminal must be connected
to terminal 3 on the zone valve. The 1361 can not be used on any
zone when the ZVR control is set for priority.