18. Replace front cover, turn on electrical supply and turn humidistat
towards 20%. (Unless remote humidistat fitted, see note 15 above) unit fan
will start, followed 6 minutes later by e compressor.
20. It is recommended at e fan mode switch is set to continuous, as in
cycle mode e fan and heaters only run togeer if ere is a demand for
dehumidification.
Safety ermostat
press to reset
(red button)
FIG 3
MODEL DH30A &
DH30AX
DH30AP &
DH30AXP
DH30ARH DH33A &
DH33AX
DH33ARH DH50A &
DH50AX
DH50AP &
DH50AXP
DH50ARH DH55A &
DH55AX
DH55ARH
SUPPLY 230V 50Hz
FUSE
Amps 10
20 10
10
10 13
32 13
13 13
NOMINAL
RUNNING AMPS
Amps 3.4 11.7 3.4 3.4 3.4 5.6 22.3 5.6 5.6 5.6
FULL LOAD AMPS Amps 4.4 12.7 4.4 4.4 4.4 7.5 24.2 7.5 7.5 7.5
COMPRESSOR LRA Amps 15.8 15.8 15.8 15.8 15.8 30 30 30 30 30
AIR FLOW
m
3
/h
700 700
700 440
440
1280 1280
1280
740 740
NOISE LEVEL @3m dB/A 52 52 52 48 48 56 56 56 48 48
WATER FLOW RATE L/min n/a n/a 10 n/a 10 n/a n/a 14 n/a 14
PRESSURE DROP m hd n/a n/a 1.6 n/a 1.6 n/a n/a 1.5 n/a 1.5
LPHW FLOW RATE L/min n/a n/a n/a 5.0 5.0 n/a n/a n/a 5.0 5.0
LPHW PRESSURE
DROP
m hd n/a n/a n/a 1.1 1.1 n/a n/a n/a 1.8 1.8
LPHW VOLUME Litres n/a n/a n/a 0.5 0.5 n/a n/a n/a 0.85 0.85
DIMENSIONS
(UNPACKED)
HEIGHT mm 655 655 655 655 655 655 655 655 655 655
WIDTH mm 780 780 780 780 780 1245 1245 1245 1245 1245
DEPTH mm 250 250 288 250 288 250 250 288 250 288
WEIGHT kg 40 40 45 40 45 60 60 65 60 65
HERMETIC
SYSTEM
REFRIGERANT
CHARGE
‘A’ DEHUMIDIFIERS
kg
R407c
0.5 0.5 1.04 0.5 1.04 0.75 0.75 1.64 0.76
1.65
REFRIGERANT
CHARGE
‘AX’
DEHUMIDIFIERS
kg 0.5 0.5 N/A 0.5 N/A 0.8 0.8 N/A 0.8 N/A
R407c Global Warming Potential (GWP) 1774
'P' MODELS WITH RESISTANCE HEATER
16. Connect remote air ermostat as shown above to mains in terminal
block marked Remote Thermostat
17. Ensure safety ermostat(s) below are set, ie push red button(s).