EasyManua.ls Logo

C&D Technologies UPS12-100MR - Table 2-Battery Parameters by Model Number

C&D Technologies UPS12-100MR
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection hardware
tightness is less than
the specified
retorque value.
Repetitive cycles
resulting in heating
and cooling of
connection can
result in relaxation of
torque and an
increase in
connection
resistance.
Loose connections can
result in heat damaged
or melted terminals
during high rate
discharge.
Retorque the
connection
as required.
Battery
Terminal
Type
Bolt Size
Annual
Retorque
in.-lbs.
Open
Circuit
Voltage
Float
Voltage
(VDC)
15 Min
Watts/Cell to
1.67 VPC*
20Hr
Ampere rate
to 1.75 VPC
Impedanc e
@ 60Hz (Ω)
Conductance
(Mhos)
UPS12-100MR
"L" #10-32 32 12.9
13.5-13.8
90.9 3 1.3 0.0060 603
UPS12-150MR
Inserted #10-32 30 12.9
13.5-13.8
148 4 1.7 0.0060 1007
UPS12-210MR
Inserted #10-32 30 12.9
13.5-13.8
206 6 2.7 0.0045 1138
UPS12-300MR
Inserted 1/4-20 110 12.9
13.5-13.8
300 9 3.9 0.0040 1669
UPS12-350MR
Inserted 1/4-20 110 12.9
13.5-13.8
350 11 4.7 0.0030 1914
UPS12-400MR
Inserted 1/4-20 110 12.9
13.5-13.8
400 12 5.2 0.0025 2079
UPS12-490MR
Inserted 1/4-20 110 12.9
13.5-13.8
488 16 7.1 0.0023 1844
UPS12-490MRLP
Inserted 1/4-20 110 12.9
13.5-13.8
488 14 5.8 0.0022 2222
UPS12-540MR
Inserted 1/4-20 110 12.9
13.5-13.8
537 17 7.5 0.0023 2032
UPS12-615MRF
Inserted TFA 1/4-20 110 12.96
13.5-13.8
614 21 8.8
0.0020
2400
UPS6-620MR
Inserted 1/4-20 110 12.9
6.75-6.90
620 22 10.0 0.0012 Limited Data
UPS12-700MRF
Inserted TFA 1/4-20 110 12.96 13.5-13.8 697 24 10.3 0.0021 2500
TEL12-30/SLC
Inserted #10-32 25 12.84
13.5-13.8
-- 4 1.7 0.0100 752
TEL12-45/SLC
Inserted #10-32 25 12.84
13.5-13.8
166 6 2.5
0.0060
858
TEL12-70
Inserted 1/4-20 110 12.84
13.5-13.8
245 9 3.8 0.0050 1326
TEL12-80/SLC
Inserted 1/4-20 110 12.84
13.5-13.8
283 10 4.4
0.0040
1467
TEL12-90
Inserted 1/4-20 110 12.84
13.5-13.8
331 11 5.0 0.0035 1549
TEL12-105FS
Inserted 1/4-20 110 12.84
13.5-13.8
-- 13 5.5
0.0034
1300
TEL12-105FNS G
Inserted TFA M8 160 12.84
13.5-13.8
339 13 5.8 0.0030 1050
TEL12-115FNG
Inserted TFA M6 110 12.84
13.5-13.8
358 14 6.0
0.0030
1090
TEL12-125
Inserted 1/4-20 110 12.84
13.5-13.8
464 16 6.7 0.0023 1747
TEL12-145FW
Inserted TFA M6 110 12.96
13.5-13.8
-- 18 7.9
0.0023
1700
TEL12-155F/FG
Inserted TFA M8 160 12.96
13.5-13.8
437 19 9.0 0.0031 1120
TEL12-160FW
Inserted TFA 1/4-20 110 12.96
13.5-13.8
-- 20 8.8
0.0027
1780
TEL12-160F
Inserted TFA 1/4-20 110 12.96
13.5-13.8
-- 20 8.6 0.0031 1500
TEL12-170F/FG
Inserted TFA M8 160 12.96
13.5-13.8
536 21 9.3
0.0033
1400
TEL12-180F
Inserted TFA 1/4-20 110 12.96
13.5-13.8
-- 23 10.0 0.0037 1510
TEL12-190F/FG
Inserted TFA M8 160 12.94
13.5-13.8
575 24 10.4
0.0035
1450
TEL12-210F/FG
Inserted TFA M8 160 12.96
13.5-13.8
605 25 11.5 0.0040 1500
TEL6-180
Inserted 1/4-20 110 12.84 6.75-6.90 -- 22 10.0 0.0012 Limited Data
DCS-33IT/HIT
Inserted #10-32 30 12.84
13.5-13.8
-- 4 1.7 0.0070 784
DCS-50IT
Inserted #10-32 30 12.84
13.5-13.8
-- 6 2.5 0.0060 916
DCS-75IT/HIT
Inserted 1/4-20 110 12.84
13.5-13.8
-- 9 3.8
0.0045
1328
DCS-88HIT
Inserted 1/4-20 110 12.84
13.5-13.8
-- 10 4.4
0.0045
1592
DCS-100HIT
Inserted 1/4-20 110 12.84 13.5-13.8 -- 11 5.0 0.0035 1515
Individual Battery Electrical Characteristics
*Excl ude s models with SLC
TABLE 2 - BATTERY PARAMETERS BY PART NUMBER
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
41-7546/0213/CD 19 www.cdtechno.com
Please refer to 12-1110 and 12-1111 for additional Ohmic reference values.