Cod. +030220151 - Rel. 2.1 - 04/09/98
47
ALARM PARAMETERS Type Min Max Unit Def New
A0 Alarm and fan differential C 0.1 +20 °C/°F 0.2
AL Low temperature alarm (deviation from set point) F 0 199 °C/°F 10
AH High temperature alarm (deviation from set point) F 0 199 °C/°F 10
Ad Temperature alarm delay C 0 199 min 120
A4 Multi-function input configuration IR32S, Y and C, IR32M C 0 5 - 0
A5 Multi-function input configuration: IRDRS, SE, IRDRC
For Rail Din mounting: must be kept 0
C 0 5 - 0
A6 Duty setting for external alarm(0=OFF, 100=ON) C 0 100 min 0
A7 External alarm delay (A4=2, Multi-function input) C 0 199 min 0
FAN PARAMETERS Type Min Max Unit Def New
F0 Fans under fan regulator (0=no, 1=yes) C 0 1 flag 0
F1 Fan shut-off temperature (relative to ambient) F 0 +20 °C/°F 5
F2 Stop fans when compressor off (0=no, 1=yes) C 0 1 flag 1
F3 Stop fans during defrost (0=no, 1=yes) C 0 1 flag 1
Fd End post-dripping F 0 15 min 3
OTHER SETTING Type Min Max Unit Def New
H0 Address within network C 0 15 - 0
H1 Type configuration: IR32S and IR32Y
IR32C and IR32P
C 0 1 flag 0
1
H2 Changing sets by keypad (0=no, 1=yes) C 0 1 flag 1
H3 Code to permit remote programming C 0 199 - 00