EasyManua.ls Logo

Carel IR33S - Carel IR33 S Factory Default Settings; Change Display from Celsius to Fahrenheit; Disable Defrost Timer; General Reset Procedure

Carel IR33S
3 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Great Water, Inc.
14 Arsene Way, Fairhaven, MA 02719
207-729-8500
info@great-water.com
Carel IR33S Electronic Thermostat Instructions
Carel IR33S Factory Default Settings
The Carel IR33S thermostat comes set up as a refrigeration thermostat, in degrees Celsius,
with 30- minute defrost period every 8 hours.
The following step by step instructions can be used to:
(1) To change display from Celsius to Fahrenheit:
• Press "PRG/mute" & "SET" together & hold down for 5 seconds until "0" flashes.
• Press "UP" arrow until display reads "22".
• Press "SET", "/2" appears in display.
• Press "UP" arrow until "/5" appears on display.
• Press "SET", "0" appears on display.
• Press "UP" arrow until "1" appears on display.
• Press "SET", "/5" appears on display.
• Hold "PRG/mute" for 5 seconds to save this change.
The display will now read in degrees Fahrenheit.
(2) To disable the defrost timer:
• Press & hold "PRG/mute" for 5 seconds until “St” appears on the display.
• Press "UP" arrow until you see “d1” ( 5 times)
• Press "SET" and you will see the number 8.
• Press "DOWN" arrow until you see “0”
• Press "SET" and you will see “d1” on the display
• Hold “PRG/mute” for 5 seconds to save this change.
Defrost timer will now be disabled.
(3) General Reset - If a programming error is made a General Reset will return all the
settings to the factory defaults.
Turn power off to thermostat.
Restore power while holding down the “PRG/mute” button.