ir33 universale  +030220801 - rel. 1.0 - 16.04.2008
1.2  Functions and main  characteristics
The IR33/DN33 controllers feature two main types of operation: “direct” 
and “reverse”, based on the value measured. In “direct” operation, the 
output is activated if the value measured exceeds the set point plus 
a di erential, and thus aims to keep the value below a certain level 
(typically used in refrigeration systems). Vice-versa, in “reverse” operation 
the output is activated when the temperature falls below the set point 
plus a di erential (typically used in heating systems).
There are nine preset operating modes in which the installer can choose 
the set point and the activation di erential.
In “special” operating mode, the exact activation point and deactivation 
and the control logic, “direct” or “reverse”, can both be set, guaranteeing 
signi cant  exibility. Finally, automatic cycles can be programmed, called 
“operating cycles”, used for example in processes where the temperature 
must remain above a certain value for a minimum time (pasteurisation). An 
operating cycle is de ned by  ve time intervals in which the temperature 
must reach a certain set point. The operating cycle is activated on the 
keypad, via digital input or automatically on the models with RTC. On all 
models, it runs for the set time , thanks to the internal timer. The remote 
control, an accessory available for all the controllers, has the same buttons 
as the controller interface, and in addition can directly display the most 
frequently used parameters. Based on the model of controller, the output 
activated may be a relay, a PWM signal for solid state relays (SSR) or a 
voltage that increases linearly from 0 to 10 Vdc. The PWM output can also 
be converted, using the following modules:
CONV0/10A0: conversion from PWM output for SSR to a linear 0 to 10 
• 
Vdc or 4 to 20 mA analogue signal;
CONONOFF0: conversion from PWM output for SSR to an ON/OFF relay • 
output. 
Below is a description of the accessories for the IR33/DN33 Universal:
ComTool programming tool 
(downloadable from http://ksa.carel.com)
With this useful tool, the controller can be programmed from any PC, 
saving the di erent con gurations to  les that can be loaded during the 
 nal programming stage, creating custom sets of parameters for faster 
programming and setting di erent user pro les with access protected 
by password. The PC must be  tted with the USB/RS485 converter code 
CVSTDUMOR0.
Remote control (code IRTRUES000)
Used to directly access the main functions, the main con guration 
parameters and to program the controller from a distance, using a group 
of buttons that exactly replicate the keypad on the controller.
 
Programming key (code IROPZKEY00) and programming key with 
power supply (code IROPZKEYA0)
The keys can be used to quickly program the controllers, even when 
not connected to the powered supply, reducing the risk of errors. These 
accessories also allow fast and e ective technical service, and can be 
used for programming the controllers in just a few seconds, also during 
the testing phase. 
 
RS485 serial interface (code IROPZ48500 & IROPZ485S0)
These   t directly into the connector that normally is used for programming 
via key, and allow connection to the PlantVisor supervisory system. These 
options have been designed to remain outside of the controller and 
consequently the connection to the PlantVisor supervisory system can 
be installed at any time, even subsequently, if the system requires. Model 
IROPZ485S0 features a microprocessor and can automatically recognise 
the TxRx+ and TxRx- signals (possibility to reverse the connection). 
 
RS485 card (code IROPZSER30)