Devices that can be connected to the pCO3
serial 3
(L & XL) serial 5
Device
connector J11
connector J10
PCO1004850
PCOS004850
PCO100MDM0
PCO10000F0
PCO10000R0
PCO100CLP0
PCO1000WB0
PCO1000BA0
PCOS00HBB0
PCO100FD10
PCOS00FD20
PCO100TLN0
PCO100MPB0
PCOS00HBF0
connector J23
connector J9
Protocol active on the pCO Notes
Display panel X Display panel
PST terminal X PST terminal Incompatible with CAREL Master 5 exp.
PLD terminal X
pCOT - pCOI terminal X Local terminal or pLAN
pGD0 - pGD1 terminal X Local terminal or pLAN With Local terminal the pGD* works in pCOT emulation mode
pGD2 - pGD3 terminal X Local terminal or pLAN
Aria terminal X
pCO in pLAN X pLAN
FCM series controllers X
EVD200 X
EVD400 X X
pLAN or CAREL Master or
CAREL Master 5 exp.
Can only be activated on one serial port. CAREL Master 5 exp.: incompatible with PST
terminal
CAREL Slave devices (tLAN) X
CAREL Master or CAREL Master
5 exp.
Can only be activated on one serial port. CAREL Master 5 exp.: incompatible with PST
terminal. If the protocol is activated, other devices cannot be supervised on J23.
CAREL Slave devices (485) X X X X X CAREL Master or CAREL Master: can only be activated on one port, BMS serial or FieldBus serial or
pLAN.
pCOexp 485 X X X X X
CAREL Master 5 exp.
CAREL Master 5 exp.: can only be activated on one port, pLAN serial or FieldBus
serial. Activating the protocol on FieldBus serial deactivates the protocol on J23.
pCOexp tLAN X CAREL Master 5 exp.
Can only be activated on one serial port; incompatible with PST terminal
μChiller2 expansion
X
Hydronic fan coil and CANbus X X CAREL Master
Can only be activated on one serial port
PlantVisor local X X X X
PlantWatch X X X X
PCGate X X X X Can only be activated
WebGate X X X X on one serial port;
GATEWAY**0 X X X X at the same time, BMS or FieldBus
LON - Echelon RS485 X
LON - Echelon FTT10 X CAREL Slave If active on pLAN serial, these protocols cannot be used
TREND X PSTN
HTTP client X GSM
BACnet/Ethernet X Modbus Slave
BACnet/IP X on BMS serial
BACnet/MSTP (RS485) X
SNMP v1, SNMP v2C X
SNMP v3 X For SNMP v3 special pCOWEB software is used
Modbus supervisor (RTU) X X X X Modbus Slave
Modbus Slave devices X X X X Modbus Master Can only be activated on one serial port
pCOexp Modbus X X X X
BenShaw devices X X Modbus Master - Benshaw Maximum of two Benshaw devices
WinLoad local XXXX XX WinLoad Can only be activated on one serial port; on FieldBus serial from Bios 4.00
WinLoad remote, analogue modem X PSTN
Can only be activated on one serial port
PlantVisor remote, analogue modem X X
Incompatible with the GSM protocol; if activated on BMS serial is incompatible with
Carel Slave set on pLAN serial
WinLoad remote, GSM modem X Can only be activated on one serial port.
PlantVisor remote, GSM modem X X GSM
Send and receive SMS X X
Incompatible with the protocol PSTN; if activated on BMS serial is incompatible with
Carel Slave set on pLAN serial
Belimo devices X MP-Bus
Maximum of 8 devices
Serial printer X X Serial printer
Can only be activated on one serial port
76
serial 0 -
pLAN serial 1 - BMS serial 2 - FieldBus